Basic Program Example - Mitsubishi Electric FX3G User Manual

Hide thumbs Also See for FX3G:
Table of Contents

Advertisement

FX
/FX
/FX
/FX
/FX
3S
3G
3GC
3U
3UC
FX
-4AD-ADP (4-channel Analog Input)
3U
• For FX
/FX
3U
3UC
The following program will set channel 1 of the 1st adapter to voltage input mode and channel 2 to current
input mode, and will store the converted A/D value of channel-1 data into D100 and that of channel-2 data
into D101.
M8001
Normally
OFF
M8000
Normally
ON
M8002
Initial
pulse
M8000
Normally
ON
M8000
Normally
ON
Even if the input data is not stored into D100 or D101, the data registers D8260 or D8261 can be directly
used in the timer/counter setting value or in a PID instruction.
PLC User's Manual - Analog Control Edition
Series PLC
M8260
M8261
RST
D8268.6
RST
D8268.7
FNC 12
K5
D8264
MOV
FNC 12
K5
D8265
MOV
FNC 12
D8260
D100
MOV
FNC 12
D8261
D101
MOV
Sets the input mode of channel
1 to the voltage input mode
(0 V to 10 V).
Sets the input mode of channel
2 to the current input mode
(4 mA to 20 mA).
Error status: b6 = OFF
Error status: b7 = OFF
Sets the averaging time to "5"
for channel-1 data.
Sets the averaging time to "5"
for channel-2 data.
Stores the A/D converted
channel-1 digital data into D100.
Stores the A/D converted
channel-2 digital data into D101.
4 Programming

4.8 Basic Program Example

C-27
A
B
C
D
E
F
G
H
I
J