Specifications; Generic Specifications - Mitsubishi Electric FX3G User Manual

Hide thumbs Also See for FX3G:
Table of Contents

Advertisement

FX
/FX
/FX
/FX
/FX
3S
3G
3GC
3U
3UC
FX
-2AD-BD (2-channel Analog Input)
3G
2.

Specifications

This chapter describes the general and performance specifications for the 2AD-BD.
2.1

Generic Specifications

Item
Ambient
0 to 55 °C (32 to 131 °F) when operating
-25 to 75 °C (-13 to 167 °F) when stored
temperature
Relative
5 to 95%RH (no condensation) when operating
humidity
Vibration
DIN Rail Mounting
*1
resistance
Direct Mounting
*1
Shock
147 m/s
resistance
Noise
Using noise simulator of:
Noise voltage: 1,000 Vp-p / Noise width: 1 μs / Rise: 1 ns / Cycle: 30 to 100 Hz
resistance
Class D grounding (grounding resistance: 100 Ω or less)
Grounding
<Common grounding with a heavy electrical system is not allowed.>
Working
Free from corrosive or flammable gas and excessive conductive dusts
environment
Working
< 2000 m
altitude
*1.
The criterion is shown in IEC61131-2.
*2.
PLC
Independent grounding
Best condition
*3.
If the pressure is higher than the atmospheric pressure, do not use the 2AD-BD.
The 2AD-BD may malfunction.
PLC User's Manual - Analog Control Edition
Frequency
(Hz)
10 to 57
57 to 150
10 to 57
57 to 150
2
Acceleration, Action time: 11 ms, 3 times by half-sine pulse in each direction X, Y, and Z
*3
Other
Other
PLC
equipment
equipment
Shared grounding
Good condition
→ For a detailed description of the grounding, refer to Section 3.5.

Specifications

Acceleration
Half amplitude
2
(mm)
(m/s
)
-
0.035
4.9
-
0.075
9.8
*2
Other
PLC
equipment
Common grounding
Not allowed
2 Specifications

2.1 Generic Specifications

Tests 10 times in each
direction (X-, Y-, and Z-
axis directions) (Total:
80 min, each)
D-7
A
B
C
D
E
F
G
H
I