Fx 2Nc -4Da - Mitsubishi Electric FX3G User Manual

Hide thumbs Also See for FX3G:
Table of Contents

Advertisement

FX
/FX
/FX
/FX
/FX
3S
3G
3GC
3U
3UC
Common Items
4.2.5
FX
-4DA
2NC
Specifications
Number of output points
Analog output range
Offset
Gain
Digital input
*1
Resolution
Ambient temperature:
25±5°C
Ambient temperature:
0 to 55°C
Reference
Time required for D/A
conversion
Output characteristics
Insulation method
Number of I/O points
occupied
*1.
Adjustment of the offset or gain value will not affect the resolution.
*2.
The offset and the gain should satisfy the following condition:
1V
(Gain - Offset)
*3.
The offset and the gain should satisfy the following condition:
4mA
(Gain - Offset)
PLC User's Manual - Analog Control Edition
Voltage output
-10V to +10V DC
(External load: 2 k to 1 MΩ)
*1*2
-5V to +5V
*1*2
-4V to +15V
With sign, 12 bits, binary
5mV (20V × 1/4000)
±0.5% (±100mV) for 20V full scale
±1.0% (±200mV) for 20V full scale
Does not include any load fluctuation.
2.1ms (The number of selected channels will not affect this value.)
When the output mode is set to "0":
+10V
-2000
0
+2000
-10V
• The photocoupler is used to insulate the analog output area from the PLC.
• The DC/DC converter is used to insulate the power supply from the analog output.
• Channels are not insulated from each other.
8 points (Taken from either the input or output points of the PLC.)
15V
32mA
4 Comparison of Performance Specifications
FX
-4DA
2NC
Current output
4ch
0mA to 20mA DC
4mA to 20mA DC
(External load: 500 Ω or less)
-20mA to +20mA
-16mA to +32mA
10 bits, binary
20μA (20mA × 1/1000)
±0.5% (±100μA) for 20mA full scale
Same accuracy for 4mA to 20mA output
±1.0% (±200μA) for 20mA full scale
Same accuracy for 4mA to 20mA output
When the output mode is "2":
(The dotted line is for mode 1.)
20mA
4mA
0
Digital input
4.2 Analog Output
*1*3
*1*3
-
1000
A-39
A
B
C
D
E
F
G
H
I
J