Relationship Between Parameter Setting And Auto-Tuning - Mitsubishi Electric FX3G User Manual

Hide thumbs Also See for FX3G:
Table of Contents

Advertisement

FX
/FX
/FX
/FX
/FX
3S
3G
3GC
3U
PID Instruction (FNC 88)
Explanation of set items
Set item
Target value
S
1
(SV)
Measured
S
2
value (PV)
S
Parameter
3
Output value
D
(MV)
*1.
When auto-tuning is not executed for the limit cycle method, the same number of devices as those
occupied in the step response method become occupied.
2.2

Relationship Between Parameter Setting and Auto-Tuning

1. When auto-tuning is not executed (parameter setting)
It is necessary to write the set value of the parameters
etc. before starting the PID operation when auto-tuning is not executed.
When data registers in the latch area are backed up against power failure, the setting data is held even after
the power of the PLC is turned OFF. Therefore, writing is not necessary when the power is turned back ON.
2. When auto-tuning is executed
The proportional gain (
constants for executing the auto-tuning function described later and for optimizing the PID control. These
constants can be set automatically.
→ For a detailed description of auto-tuning (step response method), refer to Section. 4.2.
M-6
PLC User's Manual - Analog Control Edition
3UC
• The target value (SV) is set.
• The PID instruction does not change the settings.
• Caution on using the auto-tuning (limit cycle method)
If the target value for auto-tuning is different from the target value in the PID
control, it is necessary to set a value to which a bias value is added, and then
store the actual target value when the auto-tuning flag turns OFF.
This is the input value of the PID operation.
1) Auto-tuning (in the limit cycle)
Twenty-nine devices are occupied from the head device specified in
2) Auto-tuning (in the step response method)
a) Operation setting (ACT): When bits 1, 2 and 15 are something other than "0"
*1
Twenty-five devices are occupied from the head device specified in
b) Operation setting (ACT): When bits 1, 2 and 15 are "0"
Twenty devices are occupied from the head device specified in
1) PID control (normal processing)
The user sets the initial output value before driving the instruction.
After that, the operation result is stored.
2) Auto-tuning (in the limit cycle method)
The Upper Limit Value (ULV) or Lower Limit Value (LLV) value is automatically
output during auto-tuning. The specified MV value is output when auto-tuning is
finished.
3) Auto-tuning (in the step response method)
The user sets the step output value before driving the instruction.
The MV value is not changed by PID instruction during auto-tuning.
+3), integral time (
S
3
→ For a detailed description of auto-tuning (limit cycle method), refer to Section. 4.1.
2.2 Relationship Between Parameter Setting and Auto-Tuning
Description
to
+6 using MOV instruction in advance,
S
S
3
3
+4) and differential time (
S
3
2 How to Use PID Instruction
Occupied
points
1
1
S
.
29
3
25
S
.
3
20
S
.
3
1
+6) are important
S
3