PID Instruction (FNC 88)
3.

Parameter

This chapter describes various parameters of PID instruction.
3.1

Parameter List: (S3) to (S3) + 28

Set item
Sampling time (T
S
3
Operation
S
+1
3
setting (ACT)
Input filter constant (α)
S
+2
3
Proportional gain (K
S
+3
3
Integral time (T
)
S
+4
I
3
Differential gain (K
S
+5
3
Differential time (T
S
+6
3
S
+7
3
:
These devices are occupied for internal processing of PID operation. Do not change data.
S
+19
3
PLC User's Manual - Analog Control Edition
Setting
)
1 to 32767 (ms)
S
0: Forward operation
bit0
1: Backward operation
0: Input variation alarm is invalid.
bit1
1: Input variation alarm is valid.
0: Output variation alarm is invalid.
bit2
1: Output variation alarm is valid.
bit3
Not available
0: Auto-tuning is not executed.
bit4
1: Auto-tuning is executed.
0: Upper and lower limits of output
value are not valid.
bit5
1: Upper and lower limits of output
value are valid.
0: Step response method
bit6
1: Limit cycle method
bit7 to bit15
Not available
0 to 99 (%)
)
1 to 32767 (%)
P
0 to 32767 (× 100 ms)
)
0 to 100 (%)
D
)
0 to 32767 (× 10 ms)
D
3.1 Parameter List: (S3) to (S3) + 28
Remarks
It cannot be shorter than operation
cycle of the PLC.
Operation direction
Do not set to ON bit 2 and bit 5 at
same time.
Do not set to ON bit 2 and bit 5 at
same time.
Select auto-tuning mode.
When "0" is set, input filter is not
provided.
When "0" is set, it is handled as "∞"
(no integration).
When "0" is set, differential gain is
not provided.
When "0" is set, differential is not
executed.
3 Parameter
K
L
M