-4DA (4-channel Analog Output)
3U
3
Determine the output characteristics to be changed.
Example: Change to output voltage of 1 to 5 V with digital values 0 to 32000
Output mode: 0
Output characteristics provided at the time
of factory shipment
Voltage output value
+10.2V
+10V
-32000
4
Determine the offset data.
Determine the analog output value for the digital output value of 0.
Set the analog output value in mV for the voltage output mode, and the analog output value in μA
for the current output mode.
Example: To set the offset value of 1 V, set 1000 mV.
5
Determine the gain data.
Determine the analog output value for the digital output value of 16000.
Set the analog output value in mV for the voltage output mode, and the analog output value in μA
for the current output mode.
Example: To set the gain value of 3 V, set 3000 mV.
(5-1)÷2+1 = 3 V (3000 mV)
E-54
PLC User's Manual - Analog Control Edition
3UC
Digital
0
value
+32000
-10V
-10.2V
→ For a detailed description of the offset data, refer to Subsection 5.4.6.
→ For a detailed description of the gain data, refer to Subsection 5.4.6.
7 Changing Output Characteristics
7.1 Procedure for Changing Output Characteristics
Output characteristics newly provided
Voltage output value
5V
1V
0
Digital
value
32000