Terminal Layout - Mitsubishi Electric FX3G User Manual

Hide thumbs Also See for FX3G:
Table of Contents

Advertisement

FX
/FX
/FX
/FX
/FX
3S
3G
3GC
3U
FX
-4DA (4-channel Analog Output)
3U
3.1

Terminal Layout

The terminals of FX
3.2
Cable and Terminal Tightening Torque
The FX
-4DA terminal block is designed for M3 screws.
3U
The end disposal of the cable shown below.
Tighten the terminal to a torque of 0.5 to 0.8 N•m.
Do not tighten terminal screws with a torque outside the above-mentioned range.
Failure to do so may cause equipment failures or malfunctions.
• When one wire is connected to one terminal
6.2 mm (0.24")
or less
6.2 mm (0.24")
or less
• When two wires are connected to one terminal
6.2 mm (0.24")
or less
6.2 mm (0.24")
or less
E-10
PLC User's Manual - Analog Control Edition
3UC
-4DA are arranged as follows:
3U
φ3.2 (0.13")
φ3.2 (0.13")
3.2 (0.13")
6.3 mm (0.25")
or more
3.2 (0.13")
6.3 mm (0.25")
or more
Signal
Application
24+
24 V DC power supply
24-
Ground terminal
V+
Channel-1 analog output
VI-
I+
Do not connect any lines.
V+
Channel-2 analog output
VI-
I+
Do not connect any lines.
V+
Channel-3 analog output
VI-
I+
Do not connect any lines.
V+
Channel-4 analog output
VI-
I+
Terminal
Crimp
screw
terminal
Terminal
Terminal
Crimp
screw
terminal
Terminal
3 Wiring
3.1 Terminal Layout

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fx3sFx3gcFx3uFx3uc

Table of Contents