Id Number - Wiegand Format Rs485 - Cerpass Reader Protocol; Id Number - Wiegand Format Rs485 - Uci Reader Protocol - Siemens AR6181-MX Installation And Configuration Manual

Table of Contents

Advertisement

Configuration parameters
10.2.10 ID number – Wiegand format RS485 – CerPass reader protocol
10.2.11 ID number – Wiegand format RS485 – UCI reader protocol
40
Siemens Building Technologies
Fire & Security Products
The ID number / card number personalized in Wiegand format is transferred.
DIP switch
DIP1 . . DIP4 = reader address, DIP5 = 0, DIP6 = 1, DIP7 = 0, DIP8 = 1
Parameter:
Transponder:
WG_CC_ss, WG_CC_ee, WG_CC_nn
WG_FC_ss, WG_FC_ee, WG_FC_nn
WG_CN_ss, WG_CN_ee, WG_CN_nn
WG_EV_ss, WG_EV_ee, WG_EV_pp
WG_OD_ss, WG_OD_ee, WG_OD_pp
Direct:
Indirect: MF_MAD, MF_AID1, MF_AID0 (Mifare – MAD), MF_BLOCK
PIN:
PIN_MODE, PIN_BUF (default = 6)
General:
CARD_TEC, TAG_BEEP, TAG_LED, CONFIG_CARD, A_ID
MF_BLOCK, MF_KEY_TYPE, MF_KEY_NO
MF_UL_BLOCK
SL_BLOCK
Transferred:
ID card data:
ID number in Wiegand format is interpreted in accordance with the
WG_xx_ss and WG_xx_ee configuration parameters, converted to a decimal
value, and sent as ASCII values; any possibly required leading zeros are to be
considered during parameterization (WG_xx_nn parameter), (telegram
identifier: Kg)
PIN:
see Setting
The ID number / card number personalized in Wiegand format is transferred.
DIP switch
DIP1 . . DIP4 = reader address, DIP5/DIP6 = 0, DIP7 = 1, DIP8 = 0
Parameter:
Transponder:
WG_CC_ss, WG_CC_ee, WG_CC_nn
WG_FC_ss, WG_FC_ee, WG_FC_nn
WG_CN_ss, WG_CN_ee, WG_CN_nn
WG_EV_ss, WG_EV_ee, WG_EV_pp
WG_OD_ss, WG_OD_ee, WG_OD_pp
WG_CODING (default = 0)
Direct:
Indirect: MF_MAD, MF_AID1, MF_AID0 (Mifare – MAD), MF_BLOCK
Interface:
None
PIN:
PIN_MODE, PIN_BUF (default = 7)
General:
CARD_TEC, TAG_BEEP, TAG_LED, CONFIG_CARD, A_ID
MF_BLOCK, MF_KEY_TYPE, MF_KEY_NO
MF_UL_BLOCK
SL_BLOCK
Transferred:
ID card data:
ID number in Wiegand format is interpreted in accordance with the
WG_xx_ss and WG_xx_ee configuration parameters, converted to a decimal
value, and sent as BCD or ASCII values; any possibly required leading zeros
are to be considered during parameterization (WG_xx_nn parameter)
PIN:
see Setting
MF_BLOCK or MF_UL_Block or SL_BLOCK
PIN input CerPass Reader Protocol in chapter 10.3.1.
MF_BLOCK or MF_UL_Block or SL_BLOCK
PIN input UCI Reader Protocol in chapter 10.3.2.
Mifare Standard
Mifare UltraLight
my-D proximity
Mifare Standard
Mifare UltraLight
my-D proximity
12.2004

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ar6182-mx

Table of Contents