Wiegand format, data on ID card (ID number in Wiegand format)
Wiegand-formatted data in conjunction with UCI reader protocol:
WG_CODING
0x00
0x01
When transferring via Wiegand interface:
WG_CD_ss
0x01 . . . 0x80
WG_CD_ss
0x01 . . . 0x80
When transferring via RS485 and Omron interface:
WG_CC_ss
0x01 . . . 0x80
WG_CC_ee
0x01 . . . 0x80
WG_CC_nn
0x01 . . . 0x10
WG_FC_ss
0x01 . . . 0x80
WG_FC_ee
0x01 . . . 0x80
WG_FC_nn
0x01 . . . 0x10
WG_CN_ss
0x01 . . . 0x80
WG_CN_ee
0x01 . . . 0x80
WG_CN_nn
0x01 . . . 0x10
WG_EV_ss
0x01 . . . 0x80
WG_EV_ee
0x01 . . . 0x80
WG_EV_pp
0x01 . . . 0x80
WG_OD_ss
0x01 . . . 0x80
WG_OD_ee
0x01 . . . 0x80
WG_OD_pp
0x01 . . . 0x80
Siemens Building Technologies
Fire & Security Products
C02 and C03
BCD-coded (4-bit) in reader protocol
ASCII-coded (7-bit) in reader protocol
Start bit digit Wiegand format data
End bit digit Wiegand format data
Start bit digit company code
End bit digit company code
Number of BCD digits for conversion, incl. leading zeros
Start bit digit facility code
End bit digit facility code
Number of BCD digits for conversion, incl. leading zeros
Start bit digit card number
End bit digit card number
Number of BCD digits for conversion, incl. leading zeros
Start bit digit for even parity bit generation
End bit digit for even parity bit generation
Bit position of even parity bit
Start bit digit for odd parity bit generation
End bit digit for odd parity bit generation
Bit position of odd parity bit
Notes:
The difference between "ee" and "ss" of a Wiegand format code may not exceed 40 bits.
The total number of BCD digits ("nn" parameter) may not exceed 16 digits (64 bits).
When data is output, the BCD value is right-aligned and leading digits are filled with = (0x30) until
"nn" digits have been reached
If the BCD value exceeds the value range defined by "nn" the higher-order digits are truncated
Data are transferred in the following order:
CompanyCode (CC), FacilityCode (FC), CardNumber (CN)
Configuration parameters
0x00: Funktion disabled
0x00: Funktion disabled
0x00: Funktion disabled
0x00: Funktion disabled
0x00: Funktion disabled
0x00: Funktion disabled
0x00: Funktion disabled
0x00: Funktion disabled
0x00: Funktion disabled
0x00: Funktion disabled
12.2004
35

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ar6182-mx

Table of Contents