Id Number - Bcd Format Rs485 - Cerpass Reader Protocol; Id Number - Bcd Format Rs485 - Uci Reader Protocol; Id Number - Bcd/Ascii Format Clock / Data: Omron Interface - Siemens AR6181-MX Installation And Configuration Manual

Table of Contents

Advertisement

10.2.7 ID number – BCD format
10.2.8 ID number – BCD format
10.2.9 ID number – BCD/ASCII format
Siemens Building Technologies
Fire & Security Products
RS485 – CerPass reader protocol
The ID number / card number personalized in BCD format is transferred.
DIP switch
DIP1 . . DIP4 = reader address, DIP5 = 0, DIP6 = 1, DIP7 = 1, DIP8 = 1
Parameter:
Transponder:
ID_START, ID_LEN
Direct:
Indirect: MF_MAD, MF_AID1, MF_AID0 (Mifare – MAD), MF_BLOCK
PIN:
PIN_MODE, PIN_BUF (default = 6)
General:
CARD_TEC, TAG_BEEP, TAG_LED, CONFIG_CARD, A_ID
MF_BLOCK, MF_KEY_TYPE, MF_KEY_NO
MF_UL_BLOCK
SL_BLOCK
Transferred:
ID card data:
16 characters in BCD format of which 13 are ID card number characters,
aligned left, filled with zeros (0x30)
PIN:
see Setting
RS485 – UCI reader protocol
The ID number / card number personalized in BCD format is transferred.
DIP switch
DIP1 . . DIP4 = reader address, DIP5/DIP6 = 0, DIP7 = 1, DIP8 = 0
Parameter:
Transponder:
ID_START, ID_LEN
Direct:
Indirect: MF_MAD, MF_AID1, MF_AID0 (Mifare – MAD), MF_BLOCK
PIN:
PIN_MODE, PIN_BUF (default = 7)
General:
CARD_TEC, TAG_BEEP, TAG_LED, CONFIG_CARD, A_ID
MF_BLOCK, MF_KEY_TYPE, MF_KEY_NO
MF_UL_BLOCK
SL_BLOCK
Transferred:
ID card data:
16 characters in ASCII format of which 13 are ID card number characters,
aligned left, filled with zeros (0x30)
PIN:
see Setting
The ID number / card number personalized in BCD or ASCII format is transferred.
DIP switch
DIP1 . . DIP3 = off, DIP4 = 1, DIP5 = 1, DIP6 = 0, DIP7 = 1 DIP8 = 0
Parameter:
Transponder:
ID_START, ID_LEN
Direct:
Indirect: MF_MAD, MF_AID1, MF_AID0 (Mifare – MAD), MF_BLOCK
Interface:
UCI_CODING (default = 0)
PIN:
PIN_MODE, PIN_BUF (default = 6)
General:
General: CARD_TEC, TAG_BEEP, TAG_LED, CONFIG_CARD, A_ID
MF_BLOCK, MF_KEY_TYPE, MF_KEY_NO
MF_UL_BLOCK
SL_BLOCK
Transferred:
ID card data:
16 characters in ASCII format of which 13 are ID card number characters,
aligned left, filled with zeros (0x30) – (telegram identifier: Kg)
PIN:
see Setting
MF_BLOCK or MF_UL_Block or SL_BLOCK
PIN input CerPass Reader Protocol in chapter 10.3.2.
MF_BLOCK or MF_UL_Block or SL_BLOCK
PIN input UCI Reader Protocol in chapter 10.3.2.
Clock / Data: Omron interface
MF_BLOCK or MF_UL_Block or SL_BLOCK
PIN input Clock / Data - Omron Interface in chapter 10.3.3.
Configuration parameters
Mifare Standard
Mifare UltraLight
my-D proximity
Mifare Standard
Mifare UltraLight
my-D proximity
Mifare standard
Mifare UltraLight
my-D proximity
12.2004