CLEARANCES
Clearances to combustible material
Always place a non-combustible insulation plate (false back wall) with a thickness of
min. 1" (2.54 cm) between the appliance and the rear wall and the side wall according
to fi gure 1. Minimum clearances to combustible material must be maintained. (See also
fi gure 13 and 14.)
Clearance to combustible ceiling: Place a non-combustible insulation plate (false
ceiling) with a thickness of min. 1¼" (3 cm) at a height of minimum 20" (50 cm) above
the appliance. Maintain a free space of 4" (10 cm) between the insulation plate and a
combustible ceiling. (See also fi gure 13 and 14.)
Combustible material
Insulation board
Appliance
Figure 1: Clearances to combustible material
Bellfi res
13
Installation instructions