Wiring
∗ Only basic insulation (Protection against Electric Shock Class I, Overvoltage
category II, Pollution degree 2) is provided on the control circuit terminals.
The supplementary insulation must be provided on the final product to comply
with CE Marking requirements.
B
A
C
1
COM NC NO
Relay output
+
0 to 5V
0 to 10V
-
+
4 to 20mA
-
♦ Terminal specifications: "Screw size: M3 (minus screw)"
♦ Frequency setting potentiometer (VR) specifications: "10kΩ, 1/4W or more
potentiometer"
♦ Relay output contact specifications: 1c no-voltage contact, 250VAC, 0.5A
(resistance load)
♦ Open collector output specifications: Maximum rating 50VDC, 50mA
Note 1) When using a 4 to 20mA signal for the frequency setting, always
connect a 200Ω, 1/4W resistor. (The inverter could be damaged if
the resistor is not connected.)
Note 2) Always read each function explanation for the parameters related to
each terminal before starting use.
Terminal
No.
1
Frequency setting potentiometer connection terminal (+5V)
2
Frequency setting analog signal input terminal
3
Common terminal for 1 , 2 , 4 to 9 signals
4
Multi-function analog signal output terminal (0 to 5V/PWM)
5
Start/stop, forward run signal input terminal
6
Forward/reverse, reverse run signal input terminal
7
Multi-function control signal SW1 input terminal
Multi-function control signal SW2 input terminal
8
Frequency setting signal changeover input terminal
Multi-function control signal SW3 input terminal
9
PWM signal input terminal
10
Open collector output terminal (C: collector)
11
Open collector output terminal (E: emitter)
A
Relay contact output terminal (NO: at factory setting)
B
Relay contact output terminal (NC: at factory setting)
C
Relay contact output terminal (COM)

Control Circuit Wiring

3
4
2
VR
-
+
Analog
output
(0 to 5V)
200Ω
"Tightening torque: 0.5 to 0.6N·m"
Terminal function
5
6
7
8
9
SW1
SW3
SW2
10 11
C
E
Open collector
output
Related parameter No.
P09
P09
P58, P59
P08
P08
P19, P20, P21
P19 to P21
P22 to P24
P19 to P21
P22 to P24
P25
P25
P26
P26
P26