Condition
Operation/setting
cannot be
performed via
Modbus
communication
(Modbus-RTU).
The earth leakage
breaker trips when
the Inverter is
operated.
DC injection
braking does not
work.
An Undervoltage
Trip (E09) occurs.
Noise enters in the
TV or radio located
near the Inverter.
An optional board
error (E60 to E68)
occurred.
An optional board
error (E69)
occurred.
SYSDRIVE MX2 Series USER'S MANUAL (3G3MX2-A@@@@)
Possible cause
Changes to
If the setting of Communication Speed
communication
Selection (C071), Communication Parity
parameters are not
Selection (C074) or Communication Stop
reflected.
Bit Selection (C075) was changed,
reconnect the power or perform a reset (by
turning the RS terminal ON and then OFF).
The setting of RUN
Set RUN Command Selection (A002/
Command Selection
A202) to "03: Modbus communication
(A002/A202) is not correct.
(Modbus-RTU)".
The setting of Frequency
Set Frequency Reference Selection (A001/
Reference Selection
A201) to "03: Modbus communication
(A001/A201) is not correct.
(Modbus-RTU)".
The communication
Set the correct communication speed in
speed is not set correctly.
Communication Speed Selection (C071).
The station number is not
Set the correct station number in
set correctly or duplicated.
Communication Station No. Selection
(C072).
The communication parity
Set the correct communication parity in
is not set correctly.
Communication Parity Selection (C074).
The communication stop
Set the correct stop bit in Communication
bit is not set correctly.
Stop Bit Selection (C075).
The wiring is incorrect.
Correctly wire the RS+ and RS− terminals
on the control circuit terminal block.
The Inverter leak current
Decrease the Carrier Frequency (b083).
is large.
Increase the sensitivity current of the earth
leakage breaker. Or, replace the earth
leakage breaker with one of higher
sensitivity current.
The DC injection braking
Set DC Injection Braking Power (A054).
power is not set.
The DC injection braking
Set DC Injection Braking Time (A055).
time is not set.
The voltage drops due to
Increase the power supply capacity.
insufficient power supply
capacity.
Irradiated noise from the
Extend as much as possible the wiring
Inverter.
distance from the TV or radio to the
Inverter.
The optional board
Refer to the manual for the optional board.
detected and error and
notified the Inverter.
Inverter failure: The
If the problem cannot be fixed in the
optional board connector
optional board, the Inverter may have
is not operating properly.
failed. The mating of the option connector
may be bad. Check of dirty contacts and
other possible causes. If the problem
cannot be solved, replace the Inverter.
Communications became
Check for bad option connector mating,
impossible after detecting
dirty terminal contacts, etc. Check to see if
the option. The optional
the terminal block cover on the Inverter and
board is partly
the cover on the optional board are mated
disconnected.
properly and the screws are properly
tightened.
7-2 Troubleshooting
Remedial actions
Reference
Page
6-3
5-22
5-15
6-3
6-3
6-3
6-3
6-2
5-51
2-17