5-6 Operation Functions

Jogging Operation (JG)

Set "06: JG" to a multi-function input terminal.
When a RUN command is issued with the JG terminal turned ON, operation starts at the
jogging frequency set by A038.
During jogging operation, the Inverter trips easily because it starts at full voltage. Adjust the set
value of Jogging Frequency (A038) to prevent the Inverter from tripping.
Output frequency
A038
Parameter
5
C001 to C007
*1.If Jogging Stop Selection (A039) is set to 02 or 05, DC injection braking data must be set. Refer to "DC
Injection Braking (DB)" on page 5-135.
Note: To perform the jogging operation, turn on the JG terminal before the FW or RV terminal.
5-59
JG input
FW input
RV input
Function name
No.
Jogging
A038
Frequency
Jogging Stop
A039
Selection
Multi-function
Input Selection
(Even when the RUN command source is the Digital Operator, issue a RUN command after turning
ON the JG terminal.) Also note that the frequency reference can be changed by F001 even during
jogging operation.
Turn ON the JG input first.
Data
Starting frequency to 9.99
00: Disabled during operation, free-run
on jogging stop
01: Disabled during operation,
deceleration stop on jogging stop
02: Disabled during operation, DC
injection braking on jogging stop
03: Enabled during operation, free-run
on jogging stop
04: Enabled during operation,
deceleration on stop jogging stop
05: Enabled during operation, DC
injection braking on jogging stop
06: JG (Jogging)
SYSDRIVE MX2 Series USER'S MANUAL (3G3MX2-A@@@@)
Default
Unit
setting
6.00
Hz
*1
04
*1