5-5 Settings Relating to Control Method

Torque Boost

Compensates for the voltage drop caused by the resistance in the 1st resistance of the motor,
or by wiring to suppress torque reduction at a low speed range.
To select the automatic torque boost for A041/A241, set Motor Capacity (H003/H203) and
Motor Pole Number (H004/H204) according to your motor.
Parameter
A041/A241
A042/A242
A043/A243
H003/H203
H004/H204 Motor Pole Number 1/2 2/4/6/8/10
A046/A246
5
A047/A247
Manual Torque Boost
Outputs the voltage set in A042/A242 or A043/A243.
In A042/A242, set a ratio based on the voltage set in the motor voltage selection as 100%. The
ratio set here corresponds to the output frequency of 0 Hz.
If you raise the set value of the manual torque boost, be careful about motor overexcitation.
Otherwise, the motor may burn out.
The Manual Torque Boost Frequency A043/A243 is set in percentage terms based on the base
frequency as 100%.
Switch between Controls 1/2 using the SET terminal which is a multi-function input terminal to
which "08: SET" is allocated.
Output
voltage (%)
A042/A242
5-49
Function name
No.
Torque Boost
Selection 1/2
Manual
Torque Boost Voltage 1/2
Manual Torque Boost
Frequency 1/2
Motor Capacity 1/2
Automatic Torque Boost
Voltage Compensation
Gain 1/2
Automatic Torque Boost
Slip Compensation Gain
1/2
100
A043/A243
Base frequency
Data
00: Manual torque boost
01: Automatic torque boost
0.0 to 20.0
Ratio to motor voltage (A082/A282)
0.0 to 50.0
Ratio to base frequency (A003/A203)
0.1 to 18.5
0. to 255.
Refer to "Automatic Torque Boost" on
page 5-50.
0. to 255.
Refer to "Automatic Torque Boost" on
page 5-50.
Output frequency
(100 %)
SYSDRIVE MX2 Series USER'S MANUAL (3G3MX2-A@@@@)
Default
Unit
setting
00
1.0
%
5.0
%
Default
kW
setting
4
pole
100.
100.