10. Mount the replacement CD-RW/DVD-RW drive unit by following the removal
instructions in
Step 8
Caution – Do not forcibly push the CD-RW/DVD-RW drive unit in when inserting
it. If the CD-RW/DVD-RW drive unit is forcibly inserted despite the presence of any
obstruction in a slot or any problems with the connector pin, serious damage may
result.
11. Switch on all main line switches for the AC section (ACS) in the power supply
system.
12. Confirm that the XSCF STANDBY LED (green) on the operator panel remains
lit. If it is blinking, wait until it remains lit.
13. Start (turn on power) all domains together. Take either of the following two
actions:
Press and hold down (for less than four seconds) the POWER switch on the
■
operator panel.
From a console that is connected to XSCF, execute the poweron -a command of
■
XSCF.
For details of the power-on operation, see
on page
4-19, and the SPARC Enterprise M3000/M4000/M5000/M8000/M9000
Servers XSCF User's Guide.
14. Start the domain as necessary.
15. Restore the original mode switch setting on the operator panel.
Note – When the maintenance work is completed, be sure to confirm the mode
switch setting and return the switch to Locked.
16. Close the door on the server, and lock it.
in reverse order.
Section 4.4.2, "Powering the Server On"
Chapter 14
CD-RW/DVD-RW Drive Unit Replacement 14-13