9. Go back to the terminal that is connected to XSCF, and perform the input
operation according to the instructions of the maintenance menu that is
displayed after the replacement.
a. Perform operation according to instructions of messages. When the display
b. Exit the maintenance menu.
10. Confirm that the replacement components are normal by using the
showhardconf or showstatus command of XSCF.
Unless "*" is displayed for the replacement FAN, it is operating normally.
For details of the showhardconf command and showstatus command, see the
SPARC Enterprise M3000/M4000/M5000/M8000/M9000 Servers XSCF User's Guide,
the SPARC Enterprise M3000/M4000/M5000/M8000/M9000 Servers XSCF Reference
Manual, or the man page.
Note – The showstatus command displays information on degraded components.
11. Close the door on the server, and lock it.
8.3

Cold Replacement

In cold replacement, none of the replacement work is performed with the
maintenance menu from a terminal connected to XSCF.
The procedure is as follows.
1. Unlock and open a door of the server.
For details, see
Caution – Before touching FRU or the dummy (filler) unit, see
"Antistatic Precautions" on page 1-6
Failure to do so might result in serious damage to operating domains.
2. Change the mode switch setting on the operator panel from Locked to Service.
Note – When the maintenance work is completed, be sure to confirm the mode
switch setting and return the switch to Locked.
8-14
SPARC Enterprise M8000/M9000 Servers Service Manual • June 2010
of the maintenance menu returns to the initial page, the operation is
completed.
Chapter
5.
and be sure to wear the antistatic wrist strap.
Section 1.4,