Trane IntelliPak Signature Series Programming Manual page 70

Commercial self-contained signature series, 20-80 ton modular series, 20-35 ton, “ao” and later design sequence
Hide thumbs Also See for IntelliPak Signature Series:
Table of Contents

Advertisement

70
Programming
(On units with electric heat)
Heat Stages
Stage Off
Factory Presets: 0%
Possible Values:
Note: Only single stage electric heat is available factory installed.
1. Press the NEXT key again to display the following screen.
(On units with an airside economizer)
OA Damper Pos 0 %
Factory Presets: OA Damper = 0%
Possible Values:
1. Press the NEXT key again to display the following screen.
(On units with VFD and bypass)
Supply Fan Bypass Relay:
Possible Values:
1. Press the NEXT key again to display the following screen.
(On units with VOM)
Ventilation Override Module Output Relay
OFF
Factory Presets: Off
Possible Values:
1. Press the NEXT key again to display the following screen.
(On units with VCM)
OA Preheater State
Factory Presets: Off
Possible Values:
1. Press the NEXT key to advance the cursor to the next field within this screen.
2. Press the NEXT key again to display the following screen.
SERVICE MODE
0-100%, Auto
OA Damper = 0-100%
NORMAL
Normal, Bypass
On, Off
OFF
On, Off
PKG-SVP01B-EN