PKG-SVP01B-EN
Programming
(On units with hydronic heat)
Supply Air Temp Reset Type:
Cooling:
ZONE
Factory Presets: None
Possible Values:
Cooling/Heating = None, Zone, OA
1. Pressing the NEXT key will display the following screen.
(On units when zone cooling reset is selected)
Supply Air Temp Zone
Start Temp:
72 F
Possible Values:
Cooling/Heating = Zone, OA
Start Temp Zone = 209 OA = 70
End Temp Zone = 210 OA = 71
1. Pressing the NEXT key will display the following screen.
Supply Air Temp Outside Air
Start Temp:
90 F
Possible Values:
Cooling/Heating = Zone, OA
Start Temp Zone = 209 OA = 70
End Temp Zone = 210 OA = 71
1. Pressing the NEXT key will display the following screen.
(On units with outside air cooling reset selected)
Supply Air Temp Zone
Maximum Amount of Reset Applied:
Possible Values:
SAT = Zone, OA
Reset (Zone) = 72
Reset (OA) = 72
1. Pressing the NEXT key will display the following screen.
(On units with outside air cooling reset selected)
Supply Air Temp Outside Air
Maximum Amount of Reset Applied:
Possible Values:
SAT = Zone, OA
Reset Zone = 72
Reset OA = 72
1. Pressing the NEXT key will display the following screen.
SETUP
Heating:
ZONE
Reset For Cooling:
End Temp: 69 F
Reset For Cooling:
End Temp: 70 F
Reset For Cooling:
5 F
Reset For Cooling:
5 F
35