24
Programming
(On units with hydronic, electric, or external heat only)
Active Morning Warmup Setpoint From
HI (KEYPAD) SETPOINT MENU
Possible Values:
Setpoint Range:
1. Pressing the NEXT key will display the following screen.
(On units with VCM module only)
Active Min OA Flow Setpoint From
REMOTE MIN POS POT INPUT
Possible Values:
Setpoint Range:
1. Pressing the NEXT key will display the following screen.
(On units with IGV or VFD only)
Active Supply Air Pressure STP From
HI (KEYPAD SETPOINT MENU
Possible Values:
1. Pressing the NEXT key will display the following screen.
On units with IGV or VFD only)
Active Supply Air Pressure Setpoints
High Limit:
40 IWC
Possible Values:
1. Pressing the NEXT key will display the following screen.
End of Submenu (NEXT) to Enter SETUP
1. Pressing the NEXT key will display the following screen.
Controlling Sensor Status Submenu
Press ENTER to View Data in This Submenu
1. Pressing the NEXT key will display the following screen.
STATUS
is
HI (Keypad) Setpoint Menu
Zone Sensor Setpoint Input
NSB Zone Sensor Setpoint Input
GBAS 0-5 VDC Module
ICS (Tracer Summit
®
)
50-90 F
HI (Keypad) Setpoint Menu
GBAS 0-5 VDC Module
0 to max unit airflow
is
HI (Keypad) Setpoint Menu
GBAS Module
Deadband:
High Limit = 1.6-4.7 IWC
Deadband = 0.1-2.0 IWC
72 F
342.0 CFM
2.0 IWC
0.5 IWC
PKG-SVP01B-EN