PKG-SVP01B-EN
Programming
Active Occupied Zone Cooling STP From
RTM ZONE TEMP INPUT
Possible Values:
HI (Keypad) Setpoint Menu
Zone Sensor Setpoint Input
NSB Zone Sensor Setpoint Input
GBAS 0-5 VDC Module
ICS (Tracer Summit
1. Pressing the NEXT key will display the following screen.
(On units with hydronic, electric, or external heat with daytime warmup
enabled only)
Active Occupied Zone Heating STP From
RTM ZONE TEMP INPUT
Possible Values:
HI (Keypad) Setpoint Menu
Zone Sensor Setpoint Input
NSB Zone Sensor Setpoint Input
GBAS 0-5 VDC Module
ICS (Tracer Summit
1. Pressing the NEXT key will display the following screen.
Active Unoccupied Zone Cooling STP From
RTM ZONE TEMP INPUT
Possible Values:
HI (Keypad) Setpoint Menu
Zone Sensor Setpoint Input
NSB Zone Sensor Setpoint Input
GBAS 0-5 VDC Module
ICS (Tracer Summit
1. Pressing the NEXT key will display the following screen.
(On units with hydronic, electric, or external heat only)
Active Unoccupied Zone Heating STP From
RTM ZONE TEMP INPUT
Possible Values:
HI (Keypad) Setpoint Menu
Zone Sensor Setpoint Input
NSB Zone Sensor Setpoint Input
GBAS 0-5 VDC Module
ICS (Tracer Summit
Setpoint Range:
50-90 F
1. Pressing the NEXT key will display the following screen.
STATUS
is
74 F
®
)
is
100 F
®
)
is
85 F
®
)
is
60 F
®
)
23