Trane IntelliPak Signature Series Programming Manual page 14

Commercial self-contained signature series, 20-80 ton modular series, 20-35 ton, “ao” and later design sequence
Hide thumbs Also See for IntelliPak Signature Series:
Table of Contents

Advertisement

Use Table P-GI-3 to reference factory default setpoints and keep track of setpoint adjustments at start-up. Make necessary adjust-
ments using the setpoint key on the HI.
Table P-GI-3. Default Setpoint Setups.
Daytime warmup - initiate
Daytime warmup - terminate
Low ambient compressor lockout (std. units)
Supply air temp - cooling
Supply air temp - heating
Unoccupied zone temp - cool
Unoccupied zone temp - heat
Unoccupied zone temp - MWU
Use Table P-GI-4 to reference function setups and keep track of start-up adjustments. Make necessary adjustments using the setup
key on the HI.
Table P-GI-4. Function (Enable/Disable) Setups.
Compressor lead/lag
Daytime warmup
Morning warmup
Supply air tempering
Unoccupied economizer
Unoccupied heating
Unoccupied mechanical cooling
14
Programming
Factory Preset
67 F
71 F
50 F
55 F
100 F
85 F
60 F
72 F
Factory Preset
Changed to:
Disable
Disable
Enable
Disable
Enable
Enable
Enable
General
Information
Changed to:
Reference Page #
57
57
60
57
57
58
58
58
Reference Page #
34
32
33
33
37
33
33
PKG-SVP01B-EN

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Intellipak signature scwg-020Intellipak signature scwg-025Intellipak signature scwg-030Intellipak signature scwg-035Intellipak signature siwg-020Intellipak signature siwg-025 ... Show all

Table of Contents