Trane IntelliPak Signature Series Programming Manual
Trane IntelliPak Signature Series Programming Manual

Trane IntelliPak Signature Series Programming Manual

Commercial self-contained, 20/35-110ton
Hide thumbs Also See for IntelliPak Signature Series:

Advertisement

Quick Links

Programming Guide
IntelliPak™
Commercial Self-Contained
Signature Series, 20-110Ton
Modular Series, 20-35Ton
Model Numbers:
SCWG -020, -025, -030, -035
SIWG -020, -025, -030, -035
SCRG -020, -025, -032
SIRG -020, -025, -032
SCWF -020, -022, -025, -029, -032, -035, -038, -042, -046, -052, -058, -065, -072, -080, -90, -C0, -C1
SIWF -020, -022, -025, -029, -032, -035, -038, -042, -046, -052, -058, -065, -072, -080, -90, -C0, -C1
SCRF -020, -025, -029, -030, -035, -040, -050, -060
SIRF -020, -025, -029, -030, -035, -040, -050, -060
Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-
conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment
by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in the literature and
on the tags, stickers, and labels that are attached to the equipment.
October 2015
SAFETY WARNING
PKG-SVP01E-EN

Advertisement

Table of Contents
loading

Summary of Contents for Trane IntelliPak Signature Series

  • Page 1 Programming Guide IntelliPak™ Commercial Self-Contained Signature Series, 20-110Ton Modular Series, 20-35Ton Model Numbers: SCWG -020, -025, -030, -035 SIWG -020, -025, -030, -035 SCRG -020, -025, -032 SIRG -020, -025, -032 SCWF -020, -022, -025, -029, -032, -035, -038, -042, -046, -052, -058, -065, -072, -080, -90, -C0, -C1 SIWF -020, -022, -025, -029, -032, -035, -038, -042, -046, -052, -058, -065, -072, -080, -90, -C0, -C1 SCRF -020, -025, -029, -030, -035, -040, -050, -060 SIRF -020, -025, -029, -030, -035, -040, -050, -060...
  • Page 2: Warnings, Cautions And Notices

    Warnings, Cautions and Notices Warnings, Cautions and Notices. unit’s human interface panel. Screens that are Note that warnings, configuration-dependent are labeled as such. Follow the cautions and notices appear at appropriate intervals appropriate steps for each screen as it appears and throughout this manual.
  • Page 3: Table Of Contents

    Table of Contents Warnings, Cautions and Notices ..2 Introduction ......2 Overview .
  • Page 4: General Information

    General Information Commonly Used Acronyms Table 1. Acronyms (continued) INFO = Information Only (Diagnostic) For convenience, a number of acronyms and abbreviations are used throughout this manual.These I/O = input/output acronyms are alphabetically listed and defined below. Indep = Independent Table 1.
  • Page 5: Glossary Of Terms

    General Information Table 1. Acronyms (continued) Table 1. Acronyms (continued) SRC = source VOM = ventilation override module Stg = stage VVDA=Variable Speed Fan (VAV)/Discharge Air Temp Control Stnd = standard W/ = with STP = SETPOINT w.c. = water column Sw = switch WU = warmup SZ = single-zone (unit airflow)
  • Page 6 BACnet Communication Interface Module The RTM is the central processor of the system. It (BCI) (Optional - used on units with Trane ICS continuously receives information from the other unit or 3rd party Building Automation Systems) modules, sensors, the remote control panel, and customer supplied relays.
  • Page 7 General Information PRESSURIZE sequence “B” At power-up, the Human Interface LCD will display one of four initial screens illustrated in the “General Status” This override sequence can be used if a positively section. pressured space is desired instead of a negatively 1.
  • Page 8: Programming The Unit

    General Information PURGE with duct pressure control “E” Figure 1. Human interface module This sequence can be used when supply air control is required for smoke control. • Supply fan – on • Supply fan VFD – on (if equipped) •...
  • Page 9: Data Manipulation Keys

    General Information DIAGNOSTICS Key Figure 2. Human interface keypad Pressing the DIAGNOSTICS key at any time will allow the operator to view any unit function failures.The LCD screen will display one of the diagnostic screens (depending on which diagnostic, if any, is present). If no key is pressed for 30 minutes while the screen is displaying diagnostic information, it will revert back to the operating status display.
  • Page 10: Unit Operation Keys

    General Information PREVIOUS Key information.The Human Interface will not display screens or parts of screens for which the unit is not configured. Pressing the PREVIOUS key causes the LCD to scroll backwards through the various displays for each menu. At Unit “Off”...
  • Page 11: Factory Presets

    General Information Factory Presets The UCM controlled unit has many operating functions which are preset at the factory, but may be modified to meet the unique requirements of each job.The following list identifies each of the unit’s adjustable functions and the value assigned to it.
  • Page 12 General Information Table 3. Factory presents (continued) Adjustable Function Factory Preset Changed To Reference Page Default Setpoint Setups Daytime warmup - initiate 67 °F p. 36 Daytime warmup - terminate 71 °F p. 36 Low ambient compressor lockout (std. units) 50 °F p.
  • Page 13: Password Protected Screens

    General Information Table 3. Factory presents (continued) Adjustable Function Factory Preset Changed To Reference Page Temporary low limit suppression 10 °F p. 26 Upper limit 120 °F p. 26 Low limit 80 °F p. 26 Condenser temperature: Efficiency check point 105 °F p.
  • Page 14: Programming Status

    Programming Status STATUS Menu general operating status display. If this happens, press the STATUS key again to return to the status menu.The following are examples of status screens that may be The STATUS menu is used to view various operating viewed by pressing the STATUS key.
  • Page 15 Programming Status Active Min OA Flow Setpoint 342.0 CCFM Used With: All units VCM module and CO reset enabled OA Flow 350.0 CCFM OA Damper Pos 0% Possible Values: Unit Airflow = 0 to maximum unit Press the NEXT key until the following screen is displayed. (If applicable) airflow Active Min OA Flow Setpoint 342.0 CCFM...
  • Page 16 Programming Status WSM Ent Cond Water Temp Input 65.2 F Used With: All water-cooled units only. Low Water Temp Compressor Lockout 34 F Possible Lockout Values: Lockout Temperature = 0 - 99 F Pressing the NEXT key will scroll forward through the screens. Compressor Module Ckt 1 Evap Temp 75.0 F Sat Cond Temp 81.0 F...
  • Page 17 Programming Status Active Outside Air Humidity Used With: Units with an airside economizer only. ECEM Return Air Humidity Possible Values: 0-100% Pressing the NEXT key will scroll forward through the screens. End of Submenu (NEXT) to Enter SETUP Pressing the NEXT key will scroll forward through the screens. Controlling Setpoint Status Submenu Press ENTER to View Data in This Submenu Pressing the NEXT key will scroll forward through the screens.
  • Page 18 Programming Status Active Min OA Flow Setpoint from Used With: Units with VCM module only Possible Values: HI (Keypad) Setpoint Menu, GBAS REMOTE MIN POS POT INPUT 342.0 CFM 0-5 VDC Module Setpoint Range: 0 to max unit airflow Pressing the NEXT key will scroll forward through the screens. Active Supply Air Pressure STP From Used With: Units with IGV or VFD only.
  • Page 19 Programming Status Active OA Temperature Sensor Input From Possible Values: RTM Outside Air Temp Input, ICS RTM OUTSIDE AIR TEMP INPUT is 86.0 F (Tracer Summit™) Pressing the NEXT key will scroll forward through the screens. Active Outside Air Humidity Sensor Input From Used With: Units with an airside economizer.
  • Page 20 Programming Status Temp Measured By Sensor Connected To Used With: On water-cooled units only. WSM ENT WATER TEMP INPUT 60.1 F Press the NEXT key until the following screen is displayed. Temp Measured By Sensor Connected To Used With: On water-cooled units only. WSM MIXED AIR TEMP INPUT 51.7 F Press the NEXT key until the following screen is displayed.(if applicable)
  • Page 21 Programming Status Active Outside Air Humidity Used With: Units with an airside economizer only Press the NEXT key until the following screen is displayed. (if applicable) Active Outside Air Humidity Used With: Units with an airside economizer and ECEM Return Air Humidity comparative enthalpy only.
  • Page 22: Programming Setup

    Programming SETUP After the unit is installed, the control module must be (language), temperature display (C or F), and system programmed with certain SETUP information in order to tuning parameters. When a SETUP screen is displayed for operate and function properly.The data necessary for unit 30 minutes without a key being pressed, the LCD screen operation will vary depending on certain factors such as will revert to the appropriate power-up display.
  • Page 23 Programming SETUP Morning Warmup Function: ENABLED Used With: Units when Electric, or Hydronic Heat is installed. Morning Warmup Type: FULL CAPACITY Factory Presets: Function = Enabled; MWU Press the NEXT key until the following screen is displayed (if applicable). Type = Full Capacity Possible Values: Function = Enabled, Disabled;...
  • Page 24 Programming SETUP Supply Air Temp Reset Type: Used With: Units without heat Factory Presets: None Cooling: ZONE Possible Values: Cooling = None, Zone, OA Press the NEXT key until the following screen is displayed. Supply Air Temp Reset Type: Used With: Units with hydronic heat Factory Presets : None Cooling: ZONE Heating: ZONE...
  • Page 25 Programming SETUP End of Submenu (NEXT) to Enter SETUP Press the NEXT key to leave the submenu and show following screen. Economizer Control Functions Submenu Used with: Units with an airside or waterside conomizer. Press ENTER to Review or Adjust Possible Values: Waterside Econ, Airside Econ Pressing the NEXT key will bypass this section.
  • Page 26: Sensor Source Selections Submenu

    Programming SETUP Water Economizer Min Position: Used With: Units with a waterside economizer Possible Values: 0-100% Press the NEXT key until the following screen is displayed. Select Water Flow Control Required For Used With: Water-cooled units with a waterside economizer installed. Water Pump System: Variable/Minimize Possible Values: Constant/Maximize;...
  • Page 27: Outside Air Ventilation Setup

    Programming SETUP For Daytime Warmup Temp Crtl, Use sensor Used With: Units with electric, Hydronic or External Heat installed. Connected to: RTM ZONE TEMP INPUT Possible Values: RTM ZONE TEMP INPUT, NSB PANEL TEMP SENSOR INPUT, RTM AUX TEMP Press the NEXT key until the following screen is displayed. INPUT, HEAT MODULE AUX TEMP INPUT, ECEM RETURN AIR TEMP INPUT For Occupied Zone Temp Ctrl, Use Sensor...
  • Page 28: Ventilation Override Definitions

    Programming SETUP OA flow Compensation Function: DISABLED Used with: All Units when an airside economizer and IGV or VFD is installed. Use fixed OA Damper Minimum Position Possible Values: ENABLED, DISABLED Enabled 2nd line= "OA Damper Min Pos Press the NEXT key until the following screen is displayed. Depends on IGV/VFD Pos.;...
  • Page 29: Gbas Module I/O Assignments

    Programming SETUP Ventilation Override Definition Mode A Used With: All Units when VOM is installed and OA preheater function is enabled VCM Preheater State IN CONTROL Factory Presets: Refer to Definitions Possible Values: OFF, IN CONTROL Press the NEXT key until the following screen is displayed. Ventilation Override Definition Mode A Used With: All Units when VOM is installed...
  • Page 30: Rtm Alarm Output Diagnostic Assignment Screens

    Programming SETUP GBAS (0 - 5 VDC) Output 1 Alarm Assignments Used With: All Units when GBAS is installed Factory Presets: Press ENTER to Review or Adjust Output 1 = Dirty Filters Output 2 = Compressor Trip Pressing the NEXT key will bypass this section. Compressor Trip - Ckt 1 Press the + or - key until the proper selection is displayed for the number 1 assignment.
  • Page 31 Programming SETUP a. if no further changes are required and you want to c. if you want to exit to another submenu in the SETUP exit back to view the unit operationg status, press menu, press the SETUP key twice.Then press the the STATUS key once, or NEXT key to scroll through the SETUP sebmenu cho98ices, or...
  • Page 32: Device Charatcteristic Setup Definitions

    Programming SETUP Temperature Calibration Offset For Used With: Water-cooled units and /or units with waterside economizer is installed Ckt 2 Sat Cond Temp Input 0.0 F Factory Presets: 0.0 F Possible Values: 0.0-5.0 F Press the NEXT key until the following screen is displayed. Temperature Calibration Offset For Used With: Water-cooled units and /or units with waterside economizer is installed...
  • Page 33 Programming SETUP Actuator Setup Water Economizer Used With: All Units when a waterside economizer is installed. Max Stroke Time 150 Sec Factory Presets: 150 Sec Possible Values: 1-255 Sec Press the NEXT key until the following screen is displayed. Actuator Setup Water Economizer Used With: All Units when a waterside economizer is installed.
  • Page 34 Programming SETUP Actuator Setup Hydronic Used With: All Units when Hydronic Heat is installed. Max Stroke Time 150 Sec Factory Presets: 150 Seconds Possible Values: 1 - 255 Seconds Press the NEXT key until the following screen is displayed. Actuator Setup Hydronic Used With: All Units when Hydronic Heat is installed.
  • Page 35: Control Algorithm Tuning Parameters

    Programming SETUP End of Submenu (NEXT) to Enter SETUP Press the NEXT key to leave the submenu and show following screen. Control Algorithm Tuning Parameters (Applicable to all units.) Control Algorithm Tuning Parameters Press ENTER to Review or Adjust Note: Contact theTrane Company before making any adjustment to these settings. Pressing the NEXT key will bypass this section.
  • Page 36: Setpoint Menu

    SETPOINT Menu The SETPOINT menu is used to designate default zone 2. Press the ENTER key to confirm your choice. If you’ve temperature SETPOINTs, supply air and space pressure made an error, press the CANCEL key to delete your SETPOINTs, and low ambient compressor lockout entry.
  • Page 37 SETPOINT Menu Default Unoccupied Zone Temp Setpoint(s) Used With: All Units when Electric, Hydronic or External Heat is installed. Cool: 85 F Heat: 60 F Morn Warmup: 72 F Factory Presets: Cool: 85 F, Heat: 60 F, Morning Warmup: 72 F Press the NEXT key until the following screen is displayed.
  • Page 38 SETPOINT Menu Low Ambient Comp Lockout Temp: 50 F Used With: All Units Comp(s) OFF if OA Temp Below This Value Factory Presets: 50 F Possible Values: -20 F to 80 F Press the NEXT key until the following screen is displayed. Setpoint Source Selections Submenu Used With: All Units Press ENTER to Review or Adjust...
  • Page 39 SETPOINT Menu For Default OA Damper Min Position, Use Used With: All Units when an airside or waterside economizer or VCM is installed. Setpoint From: HI (KEYPAD) SETPOINT MENU Factory Presets: HI (KEYPAD) SETPOINT MENU Press the NEXT key until the following screen is displayed. Possible Values: HI (KEYPAD) SETPOINT MENU, REMOTE MIN POS POT INPUT For Min Outside Air Flow Rate Ctrl, Use...
  • Page 40: Programming Configuration

    Programming Configuration The electronically controlled unit has many operating To change the sepoint values on a particular screen: functions whose settings are preset at the factory.The 1. Press the plus or minus key until the correct value following configuration programming steps are provided appears in the screen.
  • Page 41 Programming Configuration Configuration - Model Num Digit Used With: Units on all water-cooled units or units Water Flow Switch INSTALLED with waterside economizer and water flow switch. Possible Values: Installed, Not Installed Press the NEXT key until the following screen is displayed. Possible Values: Hydronic, Electric None, External Configuration - Model Num Digit Heating Type:...
  • Page 42 Programming Configuration Used With: All Units Configuration - Model Num Digit Possible Values: installed, Not Installed Remote Human Interface INSTALLED Press the NEXT key until the following screen is displayed. Used With: All units unless RTM has been changed. Unit Model Number Possible Values: Model Number Pressing the NEXT key will scroll forward through the screens.
  • Page 43: Service Mode Menu

    SERVICE MODE Menu The SERVICE MODE menu is used to input operating 1. Press the plus or minus key until the correct value parameters for unit operation during a service test. appears in the screen. Depending on the particular test being conducted, the user 2.
  • Page 44 SERVICE MODE Menu Condenser Fan Speed Used With: Air-cooled units. Ckt 1 0 % Factory Presets: 0% Possible Values: AUTO, 0-100% Press the NEXT key until the following screen is displayed Condenser Fan Speed Used With: Air-cooled units. Ckt1 0% Ckt2 0% Factory Presets: 0% Press the NEXT key to advance the cursor.
  • Page 45: Diagnostics Menu

    DIAGNOSTICS Menu The DIAGNOSTICS menu is used to view diagnostics that The word “MORE” is displayed on all screens if more than have resulted from system failures within the unit.There one diagnostic exist, except for the last diagnostic. Upon are two lists where diagnostics reside; the Active list, and reaching the last diagnostic, the word “MORE”...
  • Page 46 DIAGNOSTICS Menu Active Diagnostic -- Manual Reset Used With: All units Factory Presets: N/A ___________________ More Possible Values: Low Pressure Control Open - Ckt 1, Ckt 2, Ckt 3, Ckt 4 Manual Reset SA Static Pressure Limit Compressor Contactor Fail - Ckt 1, Ckt 2, Ckt 3, Ckt 4 Low Air Temperature Limit Trip Compressor Trip - Ckt 1, Ckt 2, Ckt 3, Ckt 4 Emergency Stop...
  • Page 47: Failure Modes

    DIAGNOSTICS Menu Log 1 ___________________ ___________________ Possible Values: Log number 1-20 Manual Viewed or Not Viewed Auto Active or History Info Or any diagnostic listed under the previous screens associated with the diagnostic type including VOM activated mode Press the CANCEL key to clear the diagnostics and prompt the following screen. Diagnostic Log is Password Protected Possible Values: + (Plus), - (Minus) Please Enter Password:...
  • Page 48: Glossary

    Glossary A heat source external to the self-contained unit that is field installed (i.e. duct heat or VAV reheat boxes). Active SETPOINT External Stop The SETPOINT which is currently being used for control A binary input on the RTM that allows unit shutdown, by the SETPOINT source selection.
  • Page 49 Glossary Applies to the control of the rooftop unit during Turning on heat when the supply air temperature drops unoccupied periods. Also refers to the NSB panel, a below a preset value usually due to cold outside air being communicating wall sensor with night setback capability. brought in to provide building ventilation.
  • Page 50: Index

    Index Symbols MCM 4 Menu Keys 8 - (Minus) Key 9 ECEM 4 Symbols Module Defaults 12 Economizer Zone Temp Setpoint Suppression 48 + (Plus) Key 9 Emergency Override modes 10 NEXT Key 8 ENTER Key Night SetBack (NSB) 48 Acronyms 4 See Figure 2 9 No Configuration 11...
  • Page 51 Supply Air Tempering 49 TCI 5 Temperature Input Calibration 30 Temperature Input Offset 13 TEST START 9 TEST START Key 10 Trane Communications Interface Module (TCI) Option 6 UCM 5 UCM Control System 5 UNIT OFF 7 Unit On 7...
  • Page 52 HVAC systems, comprehensive building services, and parts. For more information, visit www.Trane.com. Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice. © 2015Trane All rights reserved...