Trane IntelliPak Signature Series Programming Manual page 37

Commercial self-contained signature series, 20-80 ton modular series, 20-35 ton, “ao” and later design sequence
Hide thumbs Also See for IntelliPak Signature Series:
Table of Contents

Advertisement

PKG-SVP01B-EN
Programming
(On units with IGV or VFD)
Max Occupied IGV/VFD Command:
Factory Presets: 100%
Possible Values:
0-100%
1. Pressing the NEXT key will display the following screen.
End of Submenu (NEXT) to Enter SETUP
1.Pressing the NEXT key will display the following screen.
(On units with an airside or waterside economizer)
Economizer Control Functions Submenu
Press ENTER to Review or Adjust
1. Pressing the NEXT key will display the following screen.
(On units with an airside and waterside economizer)
Economizer Priority
Choose Which Economizer Stages Up First
Possible Values:
Waterside Econ, Airside Econ
1. Pressing the NEXT key will display the following screen.
(On units with a waterside economizer)
Unocc Water Economizer Function:
Factory Presets: Enabled
Possible Values:
Enabled, Disabled
1. Pressing the NEXT key will display the following screen.
(On units with an airside economizer)
Unocc Air Economizer Function:
Factory Presets: Enabled
Possible Values:
Enabled, Disabled
1. Pressing the NEXT key will display the following screen.
(On units with a waterside economizer)
Disable WS Econ If Difference Between MA
Temp and Ent Water Temp Less Than 4.0 F
1. Pressing the NEXT key will display the following screen.
SETUP
100 %
ENABLED
ENABLED
37