Trane IntelliPak Signature Series Programming Manual page 31

Commercial self-contained signature series, 20-80 ton modular series, 20-35 ton, “ao” and later design sequence
Hide thumbs Also See for IntelliPak Signature Series:
Table of Contents

Advertisement

PKG-SVP01B-EN
Programming
(On units with GBAS module)
GBAS 0 - 5VDC Module
Assignment:
Possible Values:
The inputs 1, 2, 3, and 4 may be assigned to:
Occ Zone Cooling Setpoint
Occ Zone Heating Setpoint
Unocc Zone Cooling Setpoint
Unocc Zone Heating Setpoint
Space Static Pressure Setpoint
Supply Air Static Pressure Setpoint
Min O/A Flow Setpoint
Not Assigned
1. Press the NEXT key to display GBAS 0-5 VDC inputs 2, 3, and 4.
2. Pressing the NEXT key will display the following screen.
(On units with GBAS module)
GBAS (0 - 5VDC) Demand Limit Input Status
Possible Values:
Open, Closed
1. Pressing the NEXT key will display the following screen.
(On units with GBAS module)
GBAS (0 - 5VDC) Module Relay Output Status
Output 1
OFF
Possible Values:
Open, Closed
1. Pressing the NEXT key will display the following screen.
End of Submenu (NEXT) to Enter SETUP
1. Pressing the NEXT key will display the following screen.
STATUS
Input 1
0.00 VDC
Not Assigned
OPEN
31