PKG-SVP01B-EN
Programming
(On all water-cooled units and/or units with a waterside economizer)
Temperature Calibration Offset For
WSM Entering Water Temp Input
Factory Preset:
0.0 F
Possible Values:
0.0-5.0 F
1. Pressing the NEXT key will display the following screen.
(On all water-cooled units and/or units with a waterside economizer)
Temperature Calibration Offset For
WSM Mixed Air Temp Input
Factory Preset:
0.0 F
Possible Values:
0.0-5.0 F
1. Pressing the NEXT key will display the following screen.
(On all water-cooled units and/or units with a waterside economizer)
Temperature Calibration Offset For
WSM Ent Cond Water Temp Input
Factory Preset:
0.0 F
Possible Values:
0.0-5.0 F
1. Pressing the NEXT key will display the following screen.
(On all water-cooled units and/or units with a waterside economizer)
Temperature Calibration Offset For
Ckt 1 Sat Cond Temp Input
Factory Preset:
0.0 F
Possible Values:
0.0-5.0 F
1. Pressing the NEXT key will display the following screen.
(On all water-cooled units and/or units with a waterside economizer)
Temperature Calibration Offset For
Ckt 2 Sat Cond Temp Input
Factory Preset:
0.0 F
Possible Values:
0.0-5.0 F
1. Pressing the NEXT key will display the following screen.
(On all water-cooled units and/or units with a waterside economizer)
Temperature Calibration Offset For
Ckt 3 Sat Cond Temp Input
Factory Preset:
0.0 F
Possible Values:
0.0-5.0 F
1. Pressing the NEXT key will display the following screen.
SETUP
0.0 F
0.0 F
0.0 F
0.0 F
0.0 F
0.0 F
49