Trane IntelliPak Signature Series Programming Manual page 53

Commercial self-contained signature series, 20-80 ton modular series, 20-35 ton, “ao” and later design sequence
Hide thumbs Also See for IntelliPak Signature Series:
Table of Contents

Advertisement

PKG-SVP01B-EN
Programming
(On units with a waterside economizer)
Actuator Setup
Direct/Reverse Acting
Factory Presets: Direct Acting
Possible Values:
Direct Acting, Reverse Acting
1. Pressing the NEXT key will display the following screen.
(On units with IGV or VFD)
Actuator Setup
Max Stroke Time
Factory Presets: 150 Sec
Possible Values:
1-255 Sec
1. Pressing the NEXT key will display the following screen.
(On units with IGV or VFD)
Actuator Setup
Min Voltage
Factory Presets: 2.0 VDC
Possible Values:
0-10 VDC
1. Pressing the NEXT key will display the following screen.
(On units with IGV or VFD)
Actuator Setup
Max Voltage
Factory Presets: 10.0 VDC
Possible Values:
0-10 VDC
1. Pressing the NEXT key will display the following screen.
(On units with IGV or VFD)
Actuator Setup
Direct/Reverse Act
Factory Presets: Direct Acting
Possible Values:
Direct Acting, Reverse Acting
1. Pressing the NEXT key will display the following screen.
(On units with hydronic heat)
Actuator Setup
Max Stroke Time
Factory Presets: 150 Sec
Possible Values:
1-255 Sec
1. Pressing the NEXT key will display the following screen.
SETUP
Water Econ Bypass
DIRECT ACTING
IGV/VFD Cmd
150 Sec
IGV/VFD Cmd
2.0 VDC
IGV/VFD Cmd
10.0 VDC
IGV/VFD Cmd
DIRECT ACTING
Hydronic
150 Sec
53