34
Programming
(On units with hydronic or electric heat)
Demand Limit Definition:
Cooling:
100 %
Factory Presets: None
Possible Values:
1. Pressing the NEXT key will display the following screen.
Compressor Lead/Lag Function:
Vary Staging Order to Distribute Runtime
Factory Presets: Function = Disabled
Possible Values:
Function = Disabled, Enabled
1. Pressing the NEXT key will display the following screen.
Reduce Multi-Unit Startup Power Demand
After Power-Up, Delay Unit Start:
Factory Presets: Start = 0 Seconds
Possible Values:
1. Pressing the NEXT key will display the following screen.
Coil Frost Cutout Temperature:
Compressors If Evap Temp Is Below:
Factory Presets: Temp = 30 F
Possible Values:
1. Pressing the NEXT key will display the following screen.
End of Submenu (NEXT) to Enter SETUP
1. Pressing the NEXT key will display the following screen.
VAV Control Functions Submenu
Press ENTER to Review or Adjust
1. Pressing the NEXT key will display the following screen.
(On units without heat)
Supply Air Temp Reset Type:
Cooling:
ZONE
Factory Presets: None
Possible Values:
1. Pressing the NEXT key will display the following screen.
SETUP
Heating: 100 %
Cooling /Heating = None, 50%, or 100%
DISABLED
Start = 0-255 Seconds
Shut Off
Temp = 25-35 F
Cooling = None, Zone, OA
0 Sec
30 F
PKG-SVP01B-EN