52
Programming
(On units with a waterside economizer)
Actuator Setup
Min Voltage
Factory Presets: 2.0 VDC
Possible Values:
1. Pressing the NEXT key will display the following screen.
(On units with a waterside economizer)
Actuator Setup
Max Voltage
Factory Presets: 10.0 VDC
Possible Values:
1. Pressing the NEXT key will display the following screen.
(On units with a waterside economizer)
Actuator Setup
Direct/Reverse Acting
Factory Presets: Direct Acting
Possible Values:
1. Pressing the NEXT key will display the following screen.
(On units with water-cooled units)
Actuator Setup
Max Stroke Time
Factory Presets: 150 Sec
Possible Values:
1. Pressing the NEXT key will display the following screen.
(On units with a waterside economizer)
Actuator Setup
Min Voltage
Factory Presets: 2.0 VDC
Possible Values:
1. Pressing the NEXT key will display the following screen.
(On units with a waterside economizer)
Actuator Setup
Max Voltage
Factory Presets: 10.0 VDC
Possible Values:
1. Pressing the NEXT key will display the following screen.
SETUP
Water Economizer
2.0 VDC
0-10 VDC
Water Economizer
10.0 VDC
0-10 VDC
Water Economizer
Direct Acting
Direct Acting, Reverse Acting
Water Econ Bypass
150 Sec
1-255 Sec
Water Econ Bypass
2.0 VDC
0-10 VDC
Water Econ Bypass
10.0 VDC
0-10 VDC
PKG-SVP01B-EN