Factory Presets - Trane IntelliPak Signature Series Programming Manual

Commercial self-contained signature series, 20-80 ton modular series, 20-35 ton, “ao” and later design sequence
Hide thumbs Also See for IntelliPak Signature Series:
Table of Contents

Advertisement

Factory Presets

The UCM controlled unit has many
operating functions that are preset at the
factory, but may be modified to meet the
specific job requirements. Tables P-GI-2,
P-GI-3, P-GI-4, and P-GI-5 identify each
adjustable unit function and the value
assigned to it. The tables also provide a
Table P-GI-2. Control Parameters Setup.
Default system mode
Demand limit definition for cooling
Demand limit definition for heating
Economizer minimum position (without IGV or VFD)*
Economizer minimum position with IGV @ 0%*
Economizer minimum position with IGV @ 100%*
Morning warmup type
Power-up start time delay
Supply air low limit*
Supply air temperature deadband for cooling*
Supply air temperature deadband for heating*
Supply air temperature O/A reset start temp cooling
Supply air temperature O/A reset end temp cooling
Supply air temperature O/A reset start temp heating
Supply air temperature O/A reset end temp heating
Supply air temperature reset type cooling
Supply air temperature reset type heating
Supply air temperature zone reset start temp cooling
Supply air temperature zone reset end temp cooling
Supply air temperature zone reset start temp heating
Supply air temperature zone reset end temp heating
Supply air temperature reset maximum amount cooling
Supply air temperature reset maximum amount heating
Unit Address
Unit Control
Note: Press the SETUP or SETPOINTS* key to adjust.
PKG-SVP01B-EN
Programming
space for recording field modifications. If
these factory presets match your
application requirements, simply press
the AUTO key on the HI to begin unit
operation (after completing the Pre-Start
and Start-Up procedures in the appropri-
ate Installation, Owner, and Diagnostic
manual). If your application requires
different settings, turn to the referenced
Factory Preset
Auto
None
None
15%
15%
10%
Full
0 seconds
50 F
8 F
4 F
90 F
70 F
10 F
60 F
none
none
72 F
69 F
65 F
68 F
5 F
10 F
1
Local
General
Information
page beside the function, press the
designated function menu key, then press
and hold the NEXT or PREVIOUS key until
its screen appears. Once the proper
screen appears, simply follow the
programming instructions given below
the applicable screen in this manual.
Changed to:
Reference Page #
32
33
34
59
59
59
33
34
59
59
57
35
35
36
36
34
35
35
35
36
36
35
36
32
32
13