Viessmann Vitodens 300 Service Instructions Manual page 93

Type wb3a, 49 and 66 kw gas fired wall mounted condensing boiler natural gas and lpg version
Hide thumbs Also See for Vitodens 300:
Table of Contents

Advertisement

Repairs
(cont.)
Extension kit for heating circuit with mixer
Checking the rotational direction of the mixer motor
A Rotational direction switch
B ON/OFF switch 8
1. Switch OFF the motor and restart it
at the main ON/OFF switch. The
device will carry out the following
self-test:
&
Mixer close (150 seconds)
&
Pump ON (10 seconds)
&
Mixer open (10 seconds)
&
Mixer close (10 seconds)
Then standard control mode recom-
mences.
2. Note the rotational direction of the
mixer motor during the self-test.
Then set the mixer manually to the
"Open" position.
Note
The flow temperature sensor must
now sense a higher temperature. If
the temperature falls, either the
motor is turning in the wrong direc-
tion or the mixer set is incorrectly
fitted.
Mixer installation instruc-
tions
3. Adjust the rotational direction of the
mixer motor (if required).
&
Switch position I for heating
return from the l.h. side (as deliv-
ered condition).
&
Switch position II for heating
return from the r.h. side.
Troubleshooting