Code 2
(cont.)
Coding in
Function mode
the as
delivered
condition
Address:
value
d4:0
*
3
Heating curve level =
0
d5:0
*
3
The external operat-
ing mode changeover
changes the heating
program to "Constant
operation with reduced
room temperature"
E1:1
*
3
With remote control:
Set day value is adjus-
table at the remote con-
trol unit from 10 to
30 °C
E2:50
*
3
With remote control
unit and for the heating
circuit, heating with
room temperature hook-
up must be encoded:
No display correction of
the actual room tem-
perature
E5:0
*
3
Without variable
speed circuit pump
E6:65
*
3
Max. speed of the
variable speed pump =
65 % of max. speed in
standard mode
E7:30
*
3
Min. speed of the vari-
able speed pump =
30 % of max. speed
*
3
E8:1
Min. speed subject to
the setting in coding
address E9
*3
Only for weather-compensated control units.
Coding
Possible change
change
Address:
value
d3:35
(see page 33)
d4:–13
Heating curve level
adjustable from –13 to 40
to
d4:40
(see page 33)
d5:1
The external operating
mode changeover
changes the heating pro-
gram to "Constant opera-
tion with standard room
temperature"
E1:0
Set day value adjustable
from 3 to 23 °C
E1:2
Set day value adjustable
from 17 to 37 °C
Display correction – 5 K
E2:0
to
or
Display correction – 0.1 K
E2:49
E2:51
Display correction +0.1 K
to
or
E2:99
Display correction +4.9 K
E5:1
With variable speed cir-
cuit pump; automatic
recognition
E6:0
Maximum speed adjusta-
to
ble from 0 to 100 % of
E6:100
max. speed
E7:0
Minimum speed adjusta-
to
ble from 0 to 100 % of
E7:100
max. speed
E8:0
Speed subject to the set-
ting in coding address E7
Coding
59