VIESMANN Service instructions for heating engineers Vitodens 300 Type WB3A, 6.6 to 35.0 kW Gas fired wall mounted condensing boiler natural gas and LPG version See applicability on the last page VITODENS 300 Please keep safe 5692 537 GB 6/2004...
Safety instructions Safety instructions Please follow these safety instructions closely to prevent accidents and material losses. & Safety instructions explained the Code of Practice by relevant trade associations and all local reg- Danger ulations. & This symbol warns against the all current safety regulations as risk of injury.
Page 3
For conversions or replace- ments, use only original spare Repair work parts from Viessmann or those which are approved by Viess- Important information mann. Repairing components which fulfil a safety function can com- promise the safe operation of your heating system.
Index Index Initial start-up, inspection, maintenance Steps - initial start-up, inspection and maintenance ........Further details regarding the individual steps ..........Coding Code 1......................40 Code 2......................43 Resetting the coding to the delivered condition ........... 63 Service scans Service level summary ................64 Temperatures, boiler coding card and brief scans ........
Initial start-up, inspection, maintenance Steps - initial start-up, inspection and maintenance For further instructions on individual steps, see pages indicated Commissioning steps Inspection steps Maintenance steps Page • 1. Filling the heating system ..........•...
Initial start-up, inspection, maintenance Further details regarding the individual steps Filling the heating system Important information Unsuitable fill water increases the level of deposits and corrosion and may lead to boiler damage. & Thoroughly flush the entire heating system prior to filling with water.
Page 8
Initial start-up, inspection, maintenance Further details regarding the individual steps (cont.) 4. If the control unit had already been 5. Close the boiler fill & drain valve switched ON before filling began: Start the control unit and in code 1, set coding address 2F:2.
Initial start-up, inspection, maintenance Further details regarding the individual steps (cont.) Venting the boiler 1. Close the shut-off valves on the heating water side. 2. Connect the drain hose on the upper valve B with a drain outlet. 3. Open valves A and B, and vent at mains pressure, until no sound of escaping air can be heard.
Initial start-up, inspection, maintenance Further details regarding the individual steps (cont.) Venting the heating system 1. Close the gas shut-off valve and 2. Activate the venting program via start the control unit. coding address 2F:1. Note To call up code 1 and for setting the coding address, see page 40.
Initial start-up, inspection, maintenance Further details regarding the individual steps (cont.) 5. Confirm with d. 4. Select the required language with Set the time and date (if required) - only for weather-compen- sated control units Note During commissioning, or after prolonged time out of use, it may be necessary to set the time and date.
Initial start-up, inspection, maintenance Further details regarding the individual steps (cont.) 4. Set the gas type via coding 5. Record the gas type in the service address 1E at the control unit. report on page 120. Note To call up code 1 and for setting the coding address, see page 40.
Page 13
Initial start-up, inspection, maintenance Further details regarding the individual steps (cont.) Differential pres- After approx. Check fan cables sure sensor 51 seconds and fan plug-in enables start Fault connections, (0.75 V across check fan terminals X8.5 and X8.6) Ignition Fault Check the ignition module (control voltage 230 V...
Initial start-up, inspection, maintenance Further details regarding the individual steps (cont.) Checking static and supply pressure Danger Higher CO emissions can lead to poisoning. Measure the CO value before and after any work on gas equipment to prevent any health hazards and to ensure the perfect operational condi- tion of the system.
Page 15
Initial start-up, inspection, maintenance Further details regarding the individual steps (cont.) 6. Check the supply (flow) pressure; it should be & 20 mbar for natural gas, & 50 mbar for LPG. Note Use suitable test equipment with a resolution of at least 0.1 mbar to measure the supply pressure.
(cont.) Checking the CO settings Vitodens 300 is factory-set for natural gas E, and can be converted to natural gas LL or LPG P using a conversion kit. During commissioning or maintenance, check the CO level at the boiler adap- tor.
Page 17
Initial start-up, inspection, maintenance Further details regarding the individual steps (cont.) 1. Connect a flue gas analyser at the flue gas aperture A on the boiler adaptor. 2. Open the gas shut-off valve, com- mission the boiler and create a heat demand.
Initial start-up, inspection, maintenance Further details regarding the individual steps (cont.) 7. Check the CO content. Should the actual value deviate by more than 1 % from the above range, imple- ment steps from page 16 (possibly replace the burner). 8.
Initial start-up, inspection, maintenance Further details regarding the individual steps (cont.) Checking the balanced flue system for soundness (annular gap check) For balanced flue systems tested together with the gas fired wall mounted boiler, some Federal States (e.g. Northrhein-Westphalia) waive the requirement for a soundness test (overpressure test) during commis- sioning by the flue gas inspector.
Initial start-up, inspection, maintenance Further details regarding the individual steps (cont.) Removing the burner and checking the burner gasket (replace gasket every two years) 5. Release four nuts H and remove 1. Switch OFF the control unit ON/ OFF switch and the mains electri- the burner.
Initial start-up, inspection, maintenance Further details regarding the individual steps (cont.) Checking the burner gauze assembly Replace the burner gauze assembly if the wire mesh is damaged. 1. Remove electrodes A. 4. Insert a new burner gauze assem- bly with a new gasket, and secure 2.
Initial start-up, inspection, maintenance Further details regarding the individual steps (cont.) Checking and adjusting the ignition and ionisation electro- A Ignition electrodes B Ionisation electrode 1. Check the electrodes for wear and 3. Check all clearances. If the gaps contamination. are not as specified or the electro- des are damaged, replace and 2.
Initial start-up, inspection, maintenance Further details regarding the individual steps (cont.) Cleaning the combustion chamber/heating surfaces and installing the burner 1. If required, clean combustion chamber A and heating surfaces B with a brush or flush with water. Important information Scratches on parts which are in contact with flue gases, can lead to corrosion.
Page 24
Initial start-up, inspection, maintenance Further details regarding the individual steps (cont.) 3. Secure the gas supply pipe with a new gasket. 4. Check the gas connections for soundness. Danger Escaping gas leads to a risk of explosion. Check all fittings for sound- ness.
Page 25
Initial start-up, inspection, maintenance Further details regarding the individual steps (cont.) Flow limiter (only for gas combination boilers) 1. Switch OFF the control unit, shut off the cold water supply line and drain the secondary (DHW) side of the boiler. 2.
Page 26
Initial start-up, inspection, maintenance Further details regarding the individual steps (cont.) Checking the ionisation current 1. Remove the cable and connect test equipment (adaptor line available as accessory). 2. Set the upper rated output. Constant temperature control units: Press K and d simultaneously &...
Page 27
Initial start-up, inspection, maintenance Further details regarding the individual steps (cont.) Matching the control unit to the heating system Note The control unit must be matched to the system equipment. Various system components are automatically recognised by the control unit, and codes are automatically set.
Page 28
Initial start-up, inspection, maintenance Further details regarding the individual steps (cont.) System design 2 With/without DHW heating with 1 heating circuit without mixer A1 and 1 heating circuit with mixer M2 Note The volume flow of the heating circuit without mixer must be at least 30 % greater than the volume flow of the heating circuit with mixer.
Page 29
Initial start-up, inspection, maintenance Further details regarding the individual steps (cont.) System design 3 With/without DHW heating with 1 heating circuit without mixer A1 and 1 heating circuit with mixer M2 and system separation Outside temperature sensor Maximum temperature controller Flow temperature sensor (underfloor heating) Cylinder temperature sensor...
Page 30
Initial start-up, inspection, maintenance Further details regarding the individual steps (cont.) System design 4 With/without DHW heating with 1 heating circuit without mixer A1 with separate heating circuit pump and 1 heating circuit with mixer M2 Outside temperature sensor Mains supply (extension kit) aVG KM BUS Flow temperature sensor Cylinder temperature sensor...
Page 31
Initial start-up, inspection, maintenance Further details regarding the individual steps (cont.) Required coding Address Max. speed of the internal circulation pump in heating 31:20 mode: 20 % System design 5 With/without DHW heating with 1 heating circuit with mixer M2 (with exten- sion kit), 1 heating circuit with mixer (Vitotronic 050) and low loss header Outside temperature sensor Extension kit for 1 heating circuit...
Page 32
Initial start-up, inspection, maintenance Further details regarding the individual steps (cont.) System design 6 With 1 heating circuit without mixer A1, solar panels and Vitocell-W 100 DHW cylinder (type CVB) installed adjacent to the boiler Outside temperature sensor Cylinder temperature sensor for aVG KM BUS solar operation Solar-Divicon...
Page 33
Initial start-up, inspection, maintenance Further details regarding the individual steps (cont.) Required coding Address Set DHW temperature 3 at 40 °C (check delivered condition) 67:40 Operation with natural gas (as delivered condition) 1E:0 Operation with LPG 1E:1 Connecting the control unit to the LON system (only for weather-compensated control units) The LON communication module (accessory) must be plugged in.
Page 34
Initial start-up, inspection, maintenance Further details regarding the individual steps (cont.) Single boiler system with Vitotronic 050 and Vitocom 300 Boiler control Vitotronic 050 Vitotronic 050 Vitocom unit User no. 1 User no. 10 User no. 11 User no. 99 Code 77:1 Code 77:10 Set code 77:11...
Page 35
Initial start-up, inspection, maintenance Further details regarding the individual steps (cont.) 1. Press L and d simultaneously for approx. 2 seconds. User check initiated. 2. Select the required user with a and b. 3. Activate checking with d. "Check" flashes until its comple- A Consecutive list number tion.
Page 36
Initial start-up, inspection, maintenance Further details regarding the individual steps (cont.) Changing slope and level 1. Modify the slope in code 1 with cod- ing address d3 (see page 40). Value adjustable from 2 to 35 (equals slope 0.2 to 3.5). 2.
Page 37
Initial start-up, inspection, maintenance Further details regarding the individual steps (cont.) Adjusting the set room temperature Standard room temperature: 1. For two heating circuits – select heating circuit: Press a. & 1r flashes on the display. & Select heating circuit A1 (heating circuit without mixer): Press d.
Page 38
Initial start-up, inspection, maintenance Further details regarding the individual steps (cont.) Reduced room temperature: 1. For two heating circuits – select heating circuit: Press a. & 1r flashes on the display. & Select heating circuit A1 (heating circuit without mixer): Press d.
Page 39
Initial start-up, inspection, maintenance Further details regarding the individual steps (cont.) Instructing the system user The system installer must hand the operating instructions to the system user and instruct them in the operation of the system. Scanning and resetting the "Maintenance" display The red fault indicator flashes when the limits set via coding address 21 and 23 have been reached.
Coding Code 1 Call up code 1 1. Press K and L simultaneously 3. Change this value with a and b; confirm with d. The display briefly for approx. 2 seconds. shows "adopted", then the address 2. Select the required coding address flashes again.
Page 41
Coding Code 1 (cont.) Summary Codes Coding in Function mode Coding Possible change the as change delivered Address: condition value Address: value System design 00:1 System design 1: 00:2 System design 1, 6: 1 heating circuit without 1 heating circuit without mixer A1, without DHW mixer A1, with DHW heat- heating...
Page 42
Coding Code 1 (cont.) Coding in Function mode Coding Possible change the as change delivered Address: condition value Address: value User no. 77:1 LON user number 77:2 LON user number, adjus- table from 1 to 99: 77:99 1 - 4 = boiler 5 = cascade 10 - ...
Coding Code 1 (cont.) Coding in Function mode Coding Possible change the as change delivered Address: condition value Address: value Slope A1 d3:14 Heating curve slope = d3:2 Heating curve slope adjustable from 0.2 to 3.5 d3:35 (see page 35) Slope M2 d3:14 Heating curve slope =...
Coding Code 2 (cont.) Overall summary The coding addresses are grouped in accordance with the following function ranges. The respective function range is displayed. Scroll through the ranges in the following sequence with a or b. Function range Coding addresses System design Boiler/burner 06 to 54...
Page 45
Coding Code 2 (cont.) Codes Coding in Function mode Coding Possible change the as change delivered Address: condition value Address: value System design 00:1 System design 1: 00:2 System design 1, 6: 1 heating circuit without 1 heating circuit without mixer A1, without DHW mixer A1, with DHW heat- heating...
Page 46
Coding Code 2 (cont.) Coding in Function mode Coding Possible change the as change delivered Address: condition value Address: value 23:0 No time interval for bur- 23:1 Time interval adjustable ner maintenance from 1 to 24 months 23:24 24:0 No "Maintenance" dis- 24:1 "Maintenance"...
Page 47
Coding Code 2 (cont.) Coding Internal Heating cir- Heating circuit Cylinder loading circula- cuit pump pump pump tion pump Heating cir- Heating circuit cuit without with mixer mixer Control Control funct. Control funct. Control funct. funct. Control Control funct. Control funct. funct.
Page 48
Coding Code 2 (cont.) Coding Internal Heating cir- Heating cir- Cylinder loading pump circulation cuit pump cuit pump pump Heating cir- Heating cir- cuit without cuit with mixer mixer Control Control Control funct. Control funct. funct. funct. Control Control Control funct. OFF funct.
Page 49
Coding Code 2 (cont.) Coding Internal Heating cir- Heating cir- Cylinder loading pump circulation cuit pump cuit pump pump Heating cir- Heating cir- cuit without cuit with mixer mixer Control funct. OFF Control funct. Coding in Function mode Coding Possible change the as change delivered...
Page 50
Coding Code 2 (cont.) Coding in Function mode Coding Possible change the as change delivered Address: condition value Address: value 58:0 Without auxiliary func- 58:1 Input of DHW set value 2; tion for DHW loading adjustable from 1 to 58:95 95 °C (observe coding address 56) 59:0...
Page 51
Coding Code 2 (cont.) Coding in Function mode Coding Possible change the as change delivered Address: condition value Address: value 6C:100 Set speed internal DHW 6C:0 Set speed adjustable loading pump 100 % from 0 to 100 % 6C:100 6F:100 Max.
Page 52
Coding Code 2 (cont.) Coding in Function mode Coding Possible change the as change delivered Address: condition value Address: value 77:1 LON user number 77:2 LON user number, adjus- table from 1 to 99: 77:99 1 - 4 = boiler 5 = cascade 10 - ...
Page 53
LON BUS to any connected Vitotro- nic 050 98:1 Viessmann system 98:1 System number adjusta- numbers (in conjunction ble from 1 to 5 with monitoring of sev- 98:5...
Page 54
Coding Code 2 (cont.) Coding in Function mode Coding Possible change the as change delivered Address: condition value Address: value 9b:0 No minimum set boiler 9b:1 Set temperature adjusta- water temperature in ble from 1 to 127 °C case of external 9b:127 demand 9C:20...
Page 55
Coding Code 2 (cont.) Coding in Function mode Coding Possible change the as change delivered Address: condition value Address: value A3:2 Outside temperature A3:-9 Heating circuit pump ON/ below 1 °C: Heating cir- OFF (see the following cuit pump ON A3:15 table) Outside temperature...
Page 56
Coding Code 2 (cont.) Parameters Heating circuit pump Address A3:... ON at OFF at 14 °C 16 °C Coding in Function mode Coding Possible change the as change delivered Address: condition value Address: value Boiler circuit, mixer circuit A4:0 With frost protection A4:1 No frost protection, adjustment only possible...
Page 57
Coding Code 2 (cont.) Parameter address With heating circuit pump logic function: Heating A5:... circuit pump OFF, if AT > RT + 3 K AT > RT + 2 K AT > RT + 1 K AT > RT AT > RT - 1 K AT >...
Page 58
Coding Code 2 (cont.) Coding in Function mode Coding Possible change the as change delivered Address: condition value Address: value A7:0 Without mixer econ- A7:1 With mixer economy omy function function (extended heat- ing circuit pump logic): Heating circuit pump also OFF, if the mixer was closed for longer than 20 minutes.
Page 59
Coding Code 2 (cont.) Coding in Function mode Coding Possible change the as change delivered Address: condition value Address: value b0:0 With remote control: b0:1 Heating mode: Weather- Heating mode/reduced compensated mode: Weather-com- Reduced mode: With room temperature hook- pensated b0:2 Heating mode: With room temperature hook-up...
Page 60
Coding Code 2 (cont.) Parameter With heating circuit pump logic function: Heating cir- address b5:... cuit pump OFF, if active RT > RT - 1 K; passive RT < RT - 2 K Actual Actual active RT > RT - 2 K; passive RT <...
Page 61
Coding Code 2 (cont.) Coding in Function mode Coding Possible change the as change delivered Address: condition value Address: value E2:99 Display correction +4.9 K E5:0 Without variable E5:1 With variable speed cir- speed circuit pump cuit pump; automatic recognition E6:65 Max.
Page 62
Coding Code 2 (cont.) Coding in Function mode Coding Possible change the as change delivered Address: condition value Address: value & Heat-up data with respective flow tem- peratures & Max. flow temperature achieved & Operating condition and outside tempera- ture during handover. The function continues after power failure or after the control unit has...
Coding Code 2 (cont.) Coding in Function mode Coding Possible change the as change delivered Address: condition value Address: value ing mode, the internal mode, the internal circu- circulation pump is per- F6:24 lation pump will be manently OFF started 1 to 24 times per day for 10 minutes respectively F6:25...
Service scans Service level summary Function Key combination Exit Page Press K and G simulta- Press d Temperatures, boiler cod- ing card and brief scans neously for approx. 2 seconds Press K and d simulta- Press d Relay test neously for approx. 2 seconds Press K and F simulta- Press d...
Service scans Temperatures, boiler coding card and brief scans Weather-compensated control units 1. Press K and G simultaneously 2. Select the required scan with a and b. for approx. 2 seconds. 3. Press d. The following values can be scanned, subject to the actual equipment level: Slope A1 –...
Page 66
Service scans Temperatures, boiler coding card and brief scans (cont.) Display screen Brief scan System design 1 to Display Max. demand temperature KM BUS indication in accor- users dance with the rele- vant design Flow Software Software Software Software Software switch version version...
Page 67
Service scans Temperatures, boiler coding card and brief scans (cont.) Display screen Brief scan Heating circuit 1 Heating circuit 2 (boiler circuit A1) (mixer circuit M2) Remote Software Remote Software control version control version 0: excl. Remote 0: excl. Remote 1: Vito- control 1: Vito-...
Page 68
Service scans Temperatures, boiler coding card and brief scans (cont.) Display screen Brief scan Flow System Software version Software switch design, Control unit version position indication User inter- in accor- face dance with the design Software Software version Software Software version Burner control unit version...
Service scans Temperatures, boiler coding card and brief scans (cont.) Display screen Brief scan Variable Software speed version pump Variable 0: excl. speed pump 1: Wilo 2: Grund- Checking outputs (relay test) Weather-compensated control units 1. Press K and d simultaneously 2.
Page 70
Service scans Checking outputs (relay test) (cont.) Display Description Solar pump ON Vitosolic Constant temperature control units 1. Press K and d simultaneously 2. Select the relay outputs with a and b. for approx. 2 seconds. Relay test enabled. 3. Press d. Relay test enabled.
Service scans Scanning operating conditions and sensors Weather-compensated control units 1. For two heating circuits – select 2. Press c. heating circuit: Press a. & 3. Select the required operating con- dition scan with a or b. 1r flashes on the display. &...
Page 72
Service scans Scanning operating conditions and sensors (cont.) Operating condition display Description (subject to system equip- ment level) Date Burner OFF or ON Int. pump OFF or ON Output 20 Int. output OFF or ON Internal extension Heating pump OFF or ON External extension or extension kit for one heat- ing circuit with mixer installed Cylinder loading pump OFF...
Page 73
Service scans Scanning operating conditions and sensors (cont.) Operating condition display (sub- Description ject to system equipment level) Actual value - collector sensor 70 °C/°F 263572 Burner hours run Burner starts 030529 001417 Hours run - solar circuit pump 002850 Solar energy in kW/h Displayed in °F if the relevant code has been selected and with the fourth display digit.
Troubleshooting Calling up fault code history The most recent 10 faults are saved and may be called up. 1. Press G and d simultaneously for approx. 2 seconds. 2. Call up the individual fault codes with a or b. Fault code order Fault code most recent 10th from most...
Page 75
Troubleshooting Calling up current fault codes (cont.) Control unit faults 1. Find current fault with c. 2. Select additional fault codes with a and b. 3. Acknowledge fault. The fault can be acknowledged with d. The fault message in the display will be hidden, but red fault indicator A continues to flash.
Troubleshooting Calling up current fault codes (cont.) 4. E in the display indicates that the burner control unit is locked out. After the fault has been removed, acknowledge by pressing reset E. Fault display design Plain text fault display & Burner control unit &...
Page 77
Troubleshooting Checking and acknowledging faults (cont.) Note The fault can be acknowledged with d. The fault message in the dis- play will be hidden, but the red fault indicator U continues to flash. A new fault message will be displayed if an Constant temperature control units acknowledged fault is not removed by the following morning.
Page 78
Troubleshooting Checking and acknowledging faults (cont.) Displayed Con- Weat- System Cause Remedy fault code her- character- com- istics Controls System flow Check the low loss without temperature header sensor (see flow tem- sensor lead page 87) perature break sensor (low loss header) Burner Boiler tem-...
Page 79
Troubleshooting Checking and acknowledging faults (cont.) Displayed Con- Weat- System Cause Remedy fault code her- character- com- istics No DHW Cylinder tem- Check sensors (see heating perature sen- page 87) sor 2/outlet sensor lead break No DHW Cylinder tem- Check sensors (see heating perature sen- page 87)
Page 80
Troubleshooting Checking and acknowledging faults (cont.) Displayed Con- Weat- System Cause Remedy fault code her- character- com- istics Burner Flue gas tem- Check the flue gas blocked perature sen- temperature sensor sor lead break (see page 89) Control Communica- Check connections tion fault –...
Page 81
Troubleshooting Checking and acknowledging faults (cont.) Displayed Con- Weat- System Cause Remedy fault code her- character- com- istics Control Communica- Check connections mode tion fault - and coding address solar control unit Control Communica- Check coding mode, tion fault - address 30 set- max.
Page 82
Troubleshooting Checking and acknowledging faults (cont.) Displayed Con- Weat- System Cause Remedy fault code her- character- com- istics Control Communica- Replace the LON mode tions fault - communication LON commu- module nication mod- Control Room tem- Check the room mode with- perature sen- temperature sensor out room...
Page 83
Troubleshooting Checking and acknowledging faults (cont.) Displayed Con- Weat- System Cause Remedy fault code her- character- com- istics Burner Internal fault Replace control unit blocked Burner in Flue gas tem- Check the heating fault state perature lim- system water level. iter has Vent the heating responded...
Page 84
Troubleshooting Checking and acknowledging faults (cont.) Displayed Con- Weat- System Cause Remedy fault code her- character- com- istics Burner in Fuel valve Check gas combi- fault state closes too late nation valve. Check both control paths. Press E. Burner in Fan speed too Check the fan, fault state...
Troubleshooting Checking and acknowledging faults (cont.) Displayed Con- Weat- System Cause Remedy fault code her- character- com- istics Burner Internal fault Remove EMC inter- blocked ference. If the equipment will not restart, check the boiler coding card and replace, or replace the control unit.
Page 86
Troubleshooting Repairs (cont.) 2. Test the resistance of the outside temperature sensor across term- inals X3.1 and X3.2 on the discon- nected plug and compare with the curve. 3. Where actual values strongly devi- ate from the curve values, discon- nect the wires at the sensor and repeat test directly at the sensor.
Page 87
Troubleshooting Repairs (cont.) Check the boiler temperature sensor, cylinder temperature sensor or the flow temperature sensor for low loss header 1. Boiler temperature sensor: Pull the leads from boiler temperature sensor A and measure the resis- tance. Cylinder temperature sensor: Pull the plug % from the cable harness on the control unit and measure the resistance.
Page 88
Troubleshooting Repairs (cont.) 2. Check the sensor resistance and compare actual values with the curve. 3. Replace the sensor in case of severe deviation. Danger The boiler temperature sen- sor is immersed in the heat- ing water (risk of scalding). Drain the boiler before repla- cing the sensor.
Page 89
Troubleshooting Repairs (cont.) 3. Replace the sensor in case of severe deviation. Note Water can leak out when replacing the outlet sensor. Close the cold water shut-off valve. Drain DHW pipe and plate heat exchanger (secondary side). Checking the flue gas temperature sensor The flue gas temperature sensor locks out the boiler when the permissible flue gas temperature is exceeded.
Page 90
Troubleshooting Repairs (cont.) 1. Pull the leads from the flue gas temperature sensor A. 2. Check the sensor resistance and compare actual values with the curve. 3. Replace the sensor in case of severe deviation.
Page 91
Troubleshooting Repairs (cont.) Checking plate heat exchanger H Heating return L Heating flow K Cold water M DHW 7. Release screws F and pull plate 1. Shut off and drain the boiler on heat exchanger G forward out of the primary and the secondary side.
Page 92
Troubleshooting Repairs (cont.) 10. Install in reverse order using new Danger gaskets. Lubricate the new gas- Escaping gas leads to a kets/seals. risk of explosion. Check the gas connections for soundness. Check all fittings and the flange for soundness. Checking the temperature limiter If the burner control unit cannot be reset after a fault shutdown, although the boiler water temperature is below...
Page 93
Troubleshooting Repairs (cont.) & Electrical connection & Correct position of the O-rings inside the adaptor & Are the test nipples closed with plugs? Replace the sensor if fault messages persist. 1. Pull off the electrical plug A. Checking O-rings: 2. Remove sensor B by pulling it upwards.
Page 94
Troubleshooting Repairs (cont.) Checking the fuse 3. Remove cover A. 1. Switch OFF the mains power. 2. Release the lateral closures and 4. Check fuse F1. pivot the control unit down.
Page 95
Troubleshooting Repairs (cont.) Extension kit for heating circuit with mixer Checking the rotational direction of 2. Note the rotational direction of the the mixer motor mixer motor during the self-test. Then set the mixer manually to the "Open" position. Note The flow temperature sensor must now sense a higher temperature.
Function description Constant temperature control units Heating mode DHW loading with gas fired combi- The set boiler water temperature will nation boilers be maintained in the heating and If the flow switch recognises that DHW operating program G, when a DHW is drawn off (>...
Page 97
Function description Constant temperature control units (cont.) A Heating programs F Setting values B Comfort mode G DHW temperature C Information H Emissions test function D Basic settings K Boiler water temperature E Confirmation/acknowledgement...
Function description Weather-compensated control units Heating mode The control unit determines a set boi- DHW loading with a gas fired boiler ler water temperature subject to out- The DHW heating will be activated if side temperature or room temperature the cylinder temperature falls 2.5 K (if a room temperature-dependent below the set cylinder temperature.
Page 99
Function description Weather-compensated control units (cont.) A Heating circuit time program H Party mode B DHW time program K Basic settings L Confirmation/acknowledgement and DHW circulation (if connected M Setting values to the control unit) C Holiday program N DHW temperature D Information O Emissions test function E Heating programs...
Function description Extensions for external connections (accessory) Internal extension H1 & The internal extension is integrated Central fault message (code 53:0) & into the control unit housing. As alter- Cylinder loading pump (code 53:3) & native, the following functions can be DHW circulation pump (code 53:1) connected to relay output sK.
Page 101
Function description Extensions for external connections (accessory) (cont.) Internal extension H2 & The internal extension is integrated Central fault message (code 53:0) & into the control unit housing. As alter- Cylinder loading pump (code 53:3) & native, the following functions can be DHW circulation pump (code 53:1) connected to relay output sK.
Function description Extensions for external connections (accessory) (cont.) External extension H1 & The external extension is connected External blocking to the boiler control unit via the KM (terminals 2 - 3) & BUS. The following functions can be External demand controlled or processed via this exten- (terminals 1 - 2) &...
Page 103
Function description Extensions for external connections (accessory) (cont.) External extension H2 & The external extension is connected External blocking to the boiler control unit via the KM (terminals 2 - 3) & BUS. The following functions can be External demand controlled or processed simulta- (terminals 1 - 2) &...
Function description Control functions External operating mode changeover The function "External operating mode changeover" is connected via input aVD of the external extension. With coding address 91 you can select, for which heating circuit the changeover of operating mode should apply: Coding Changeover of operating mode affects:...
Page 105
Function description Control functions (cont.) External blocking The function "External blocking" is In coding address 32 you can select connected via input aVD of the exter- the influence the signal "Ext. block- nal extension. ing" should have on the connected cir- culation pumps.
Page 106
Function description Control functions (cont.) The diverter valve can be moved into its central position via coding address 2F:2. The system can be filled com- pletely, if the control unit is switched OFF in this position. Filling with the control unit switched ON If the system is to be filled with the control unit switched ON, the diverter valve is moved into its central position...
Page 107
Function description Control functions (cont.) Temperature profile: Diagram 2 code F1:2 Temperature profile: Diagram 3 code F1:3 Temperature profile: Diagram 4 code F1:4...
Page 108
Function description Control functions (cont.) Temperature profile: Diagram 5 code F1:5 Temperature profile: Factory-set code F1:6 to F1:15...
Designs Connection and wiring diagrams – external connections Main PCB Mains supply unit...
Page 112
Designs Connection and wiring diagrams – external connectio . . . (cont.) Optolink Cylinder temperature sensor sÖ Burner control unit Internal circulation pump User interface Gas solenoid valve fÖ Coding card Power supply Connection adaptor Mains power supply - acces- LON communication module sories and Vitotrol 100 a-Ö...
Parts lists Parts lists Spare parts information Quote the type and serial no. (see type plate) and the item no. of the required part (as per this parts list). Obtain standard parts from your local supplier. 001 Quick-acting air vent valve 034 Return pipe 002 Connecting pipe 035 Ventilation air gasket...
Commissioning/service reports Commissioning/service reports Setting and test values Set value Initial start-up Date: Static pressure mbar max. 57.5 mbar Supply pressure (flow pressure) = for natural gas E mbar 17.4 to 57.5 mbar = for natural gas LL mbar 17.4 to 57.5 mbar = for LPG mbar...
Page 121
Commissioning/service reports Commissioning/service reports (cont.) Maintenance/ser- Maintenance/ Maintenance/ Maintenance/ser- vice service service vice...
Page 122
Commissioning/service reports Commissioning/service reports (cont.) Setting and test values Set value Maintenance/ service Date: Static pressure mbar max. 57.5 mbar Supply pressure (flow pressure) = for natural gas E mbar 17.4 to 57.5 mbar = for natural gas LL mbar 17.4 to 57.5 mbar = for LPG...
Page 123
Commissioning/service reports Commissioning/service reports (cont.) Maintenance/ser- Maintenance/ Maintenance/ Maintenance/ser- vice service service vice...
Page 124
Commissioning/service reports Commissioning/service reports (cont.) Setting and test values Set value Maintenance/ service Date: Static pressure mbar max. 57.5 mbar Supply pressure (flow pressure) = for natural gas E mbar 17.4 to 57.5 mbar = for natural gas LL mbar 17.4 to 57.5 mbar = for LPG...
Page 125
Commissioning/service reports Commissioning/service reports (cont.) Maintenance/ser- Maintenance/ Maintenance/ Maintenance/ser- vice service service vice...
Specification Specification Rated voltage: 230 V~ Electronic tempera- Rated frequency: 50 Hz ture limiter setting: 82 °C (fixed) Rated current : 6.0 A~ Temperature limiter Safety class: setting: 100 °C (fixed) IP X 4 D to Mains fuse: max. 16 A Protection level: EN 60529 Power consumption...
Certificates Declaration of conformity Declaration of conformity for Vitodens 300 We, Viessmann Werke GmbH & Co KG, D-35107 Allendorf, declare as sole responsible body, that the product Vitodens 300 conforms to the following stan- This product is designated in accor-...
Certificates Manufacturer's certificate according to the 1st BImSchV [Germany] We, Viessmann Werke GmbH & Co KG, D-35107 Allendorf, confirm that the fol- lowing product meets the NO limits specified by 1st BImSchV Paragraph 7 (2) [Germany]: Vitodens 300 Allendorf, 14.01.04 Viessmann Werk GmbH&Co KG...