Type wb3a, 49 and 66 kw gas fired wall mounted condensing boiler natural gas and lpg version
Hide thumbs Also See for Vitodens 300:
Table of Contents

Advertisement

Coding
Code 2
(cont.)
Coding in
Function mode
the as
delivered
condition
Address:
value
73:0
*
1
DHW circulation
pump: ON according to
time program
General
76:0
Without LON communi-
cation module
77:1
LON user number
79:1
Control unit is fault
manager
*
1
7b:1
Send time to LON
*
1
7E:0
*
2
Without flue gas cas-
cade
7F:1
*
2
Detached house
*1
Only for weather-compensated control units.
*2
Only for constant temperature control units.
50
Coding
Possible change
change
Address:
value
73:1
During the time program
to
1x/h ON for 5 minutes
73:6
up to 6x/h ON for 5 min-
utes
73:7
Constantly ON
76:1
With LON communication
module; automatic recog-
nition
76:2
With KM BUS/cascade
communication module;
automatic recognition
77:2
LON user number, adjus-
to
table from 1 to 99:
77:99
1 - 4 = boiler
5 = cascade
10 - ... = Vitotronic 050
99 = Vitocom
Note
Allocate each number
only once.
79:0
Control unit is not fault
manager
7b:0
Do not send time to LON
7E:1
With flue gas cascade
7F:0
Multi-occupancy house
Separate adjustment for
holiday program and time
program for DHW load-
ing, as option