Viessmann Vitodens 300 Service Instructions Manual page 80

Type wb3a, 49 and 66 kw gas fired wall mounted condensing boiler natural gas and lpg version
Hide thumbs Also See for Vitodens 300:
Table of Contents

Advertisement

Troubleshooting
Checking and acknowledging faults
Displayed
Const.
fault code
C6
C7
X
Cd
X
CE
X
CF
dA
db
80
Weat-
System
her-
character-
comp.
istics
X
Control
mode,
max. pump
speed
X
Control
mode,
max. pump
speed
X
Control
mode
X
Control
mode
X
Control
mode
X
Control
mode with-
out room
influence
X
(cont.)
Cause
Remedy
Communication
Check coding
fault - variable
address E5
speed heating cir-
settings;
cuit pump, heating
check the
circuit M2
heating cir-
cuit pump
DIP switch
settings
Communication
Check coding
fault - variable
address E5
speed heating cir-
settings;
cuit pump, heating
check the
circuit A1
heating cir-
cuit pump
DIP switch
settings
Communication
Check con-
fault Vitocom 100
nections and
(KM BUS)
Vitocom 100
Communication
Check con-
fault - ext. exten-
nections and
sion
coding
address 2E
settings
Communications
Replace the
fault - LON commu-
LON commu-
nication module
nication mod-
ule
Room temperature
Check the
sensor heating cir-
room tem-
cuit A1 shorted out
perature sen-
sor - heating
circuit A1
Heating circuit M2
Check the
room temperature
room tem-
sensor shorted out
perature sen-
sor - heating
circuit M2