Viessmann Vitodens 300 Service Instructions Manual page 32

Type wb3a, 49 and 66 kw gas fired wall mounted condensing boiler natural gas and lpg version
Hide thumbs Also See for Vitodens 300:
Table of Contents

Advertisement

Initial start-up, inspection, maintenance
Further details regarding the individual steps
Boiler control
Vitotronic 050
unit
User no. 1
User no. 10
Code 77:1
Code 77:10
Control unit is
Control unit is not
*
1
fault manager
fault manager
Code 79:1
Code 79:0
Sent time via LON
Time received via
Code 7b:1
LON
Set code 81:3
Transmit outside
Outside tempera-
temperature via
ture is received via
LON
LON
Set code 97:2
Set code 97:1
Fault monitoring
Fault monitoring
LON user code
LON user code
9C:20
9C:20
Implementing a user check (in conjunction with the LON sys-
tem)
Communication with the system devices connected to the fault manager is
tested with a user check.
Preconditions:
&
The control unit must be encoded as fault manager (code 79:1).
&
The LON user number must be encoded in all control units (see page 31).
&
The fault manager user list must be up to date (see page 31).
In each heating system, only one Vitotronic may be encoded as fault manager.
*1
32
Vitotronic 050
User no. 11
Set code 77:11
Control unit is not
*
1
*
fault manager
Code 79:0
Time received via
LON
Set code 81:3
Outside tempera-
ture is received via
LON
Set code 97:1
Fault monitoring
LON user code
9C:20
(cont.)
Vitocom
User no. 99
Control unit is
fault manager
1
Time received
via LON