Initial start-up, inspection, maintenance
Further details regarding the individual steps
Boiler control
Vitotronic 050
unit
User no. 1
User no. 10
Code 77:1
Code 77:10
Control unit is
Control unit is not
*
1
fault manager
fault manager
Code 79:1
Code 79:0
Sent time via LON
Time received via
Code 7b:1
LON
Set code 81:3
Transmit outside
Outside tempera-
temperature via
ture is received via
LON
LON
Set code 97:2
Set code 97:1
Fault monitoring
Fault monitoring
LON user code
LON user code
9C:20
9C:20
Implementing a user check (in conjunction with the LON sys-
tem)
Communication with the system devices connected to the fault manager is
tested with a user check.
Preconditions:
&
The control unit must be encoded as fault manager (code 79:1).
&
The LON user number must be encoded in all control units (see page 31).
&
The fault manager user list must be up to date (see page 31).
In each heating system, only one Vitotronic may be encoded as fault manager.
*1
32
Vitotronic 050
User no. 11
Set code 77:11
Control unit is not
*
1
*
fault manager
Code 79:0
Time received via
LON
Set code 81:3
Outside tempera-
ture is received via
LON
Set code 97:1
Fault monitoring
LON user code
9C:20
(cont.)
Vitocom
User no. 99
Control unit is
fault manager
1
Time received
via LON
—
—