Viessmann Vitodens 300 Service Instructions Manual page 54

Type wb3a, 49 and 66 kw gas fired wall mounted condensing boiler natural gas and lpg version
Hide thumbs Also See for Vitodens 300:
Table of Contents

Advertisement

Coding
Code 2
(cont.)
Parameters
Address A3:...
-9
-8
-7
-6
-5
-4
-3
-2
-1
0
1
2
to
15
Coding in
Function mode
the as
delivered
condition
Address:
value
Boiler circuit, mixer circuit
*
1
A4:0
With frost protection
*1
Only for weather-compensated control units.
54
Heating circuit pump
ON at
-10 °C
-9 °C
-8 °C
-7 °C
-6 °C
-5 °C
-4 °C
-3 °C
-2 °C
-1 °C
0 °C
1 °C
to
14 °C
Coding
change
Address:
value
A4:1
OFF at
-8 °C
-7 °C
-6 °C
-5 °C
-4 °C
-3 °C
-2 °C
-1 °C
0 °C
1 °C
2 °C
3 °C
16 °C
Possible change
No frost protection,
adjustment only possible
if code A3:-9 is selected.
Note
When selecting a value
below 1 °C there will be a
risk of pipes outside the
thermal insulation envel-
ope of the house freez-
ing-up. The standby
mode, in particular,
should be observed, e.g.
during holidays.