Viessmann Vitodens 300 Service Instructions Manual page 76

Type wb3a, 49 and 66 kw gas fired wall mounted condensing boiler natural gas and lpg version
Hide thumbs Also See for Vitodens 300:
Table of Contents

Advertisement

Troubleshooting
Checking and acknowledging faults
Constant temperature control units
Displayed
Const.
fault code
0F
X
10
X
18
X
20
X
28
X
76
Note
The fault can be acknowledged
with d. The fault message in the dis-
play will be hidden, but the red fault
indicator U continues to flash. A new
fault message will be displayed if an
acknowledged fault is not removed by
the following morning.
Calling up acknowledged fault mes-
sages
Press d for approx. 2 seconds;
select the acknowledged fault with a
or b.
Weat-
System
her-
character-
comp.
istics
X
Control
mode
X
Controls
according
to 0 °C out-
side tem-
perature
X
X
Controls
without
flow tem-
perature
sensor
(low loss
header)
X
(cont.)
Cause
Remedy
Maintenance
Carry out
maintenance.
Set code 24:0
after mainte-
nance
Outside tempera-
Check the
ture sensor shorted
outside tem-
out
perature sen-
sor (see
page 85)
Outside tempera-
ture sensor lead
break
System flow tem-
Check the
perature sensor
low loss
shorted out
header sen-
sor (see
page 87)
System flow tem-
perature sensor
lead break