Viessmann Vitodens 300 Service Instructions Manual page 84

Type wb3a, 49 and 66 kw gas fired wall mounted condensing boiler natural gas and lpg version
Hide thumbs Also See for Vitodens 300:
Table of Contents

Advertisement

Troubleshooting
Checking and acknowledging faults
Displayed
Const.
fault code
FA
X
Fd
X
FE
X
84
Weat-
System
her-
character-
comp.
istics
X
Burner in
fault state
X
Burner
blocked
X
Burner
blocked
(cont.)
Cause
Remedy
Fan speed too high
Check the
at burner start
fan, check the
fan cables,
check the fan
control.
Press E.
Burner control unit
Check the
fault
ignition elec-
trodes and
leads. Check
whether a
strong inter-
ference
(EMC) field
exists near
the equip-
ment.
Press E.
If the fault is
not removed,
replace the
control unit.
Strong interference
Remove EMC
(EMC) field nearby;
interference.
alternatively boiler
If the equip-
coding card or
ment will not
main PCB faulty
restart, check
the boiler
coding card
and replace,
or replace the
control unit.