Viessmann Vitodens 300 Service Instructions Manual page 44

Type wb3a, 49 and 66 kw gas fired wall mounted condensing boiler natural gas and lpg version
Hide thumbs Also See for Vitodens 300:
Table of Contents

Advertisement

Coding
Code 2
(cont.)
Coding in
Function mode
the as
delivered
condition
Address:
value
21:0
No maintenance indica-
tion
Burner
23:0
No time interval for bur-
ner maintenance
24:0
No "Maintenance" dis-
play
25:0
*
1
No recognition of out-
side temperature sen-
sor or remote
monitoring
28:0
No burner interval igni-
tion
2E:0
Without external exten-
sion
2F:0
Venting program dis-
abled
30:1
Internal variable speed
circulation pump (auto-
matic adjustment)
31:65
Set speed of the inter-
nal circulation pump
when operated as boiler
circuit pump 65 %,
defaulted by the boiler
coding card
*1
Only for constant temperature control units.
44
Coding
Possible change
change
Address:
value
21:1
The number of hours run
to
before the burner should
21:100
be serviced is adjustable
from 100 to 10000 hours
(each step represents
100 hours)
23:1
Time interval adjustable
to
from 1 to 24 months
23:24
24:1
"Maintenance" display
(the address is automati-
cally set and must be
manually reset after
maintenance has been
completed)
25:1
Recognition of outside
temperature sensor and
fault monitoring
28:1
The burner is forced ON
once every 24 hours
2E:1
Including external exten-
sion (automatical adjust-
ment on connection)
2F:1
Venting program enabled
2F:2
Filling program enabled
30:0
Internal circulation pump
without variable speed
(e.g. temporarily for ser-
vice)
31:0
Set speed adjustable
to
from 0 to 100 %
31:100