Troubleshooting
Repairs
(cont.)
Checking the thermocouple
Checking and replacing pressure differential sensor
Check the sensor in case of fault messages concerning the differential pressure
sensor:
&
Correct installation
&
Electrical connection
&
Correct position of the O-rings inside the adaptor
&
Are the test nipples closed with plugs?
Replace the sensor if fault messages persist.
90
If the burner control unit cannot be
reset after a fault shutdown, although
the boiler water temperature is below
approx. 90 °C:
&
Pull the leads from
thermocouple A.
&
Check the continuity of the thermo-
couple with a multimeter.
&
Remove the faulty thermocouple.
&
Install a new thermocouple.
&
After commissioning, press reset
button E on the control unit.