Code 2
(cont.)
Coding in
Function mode
the as
delivered
condition
Address:
value
A2:2
With DHW cylinder
priority applicable to
heating circuit pump
and mixer
A3:2
*
2
Outside temperature
below 1 °C: Heating cir-
cuit pump ON
Outside temperature
above 3 °C: Heating cir-
cuit pump OFF
Note
When selecting a value
below 1 °C there will be
a risk of pipes outside
the thermal insulation
envelope of the house
freezing-up. The
standby mode, in parti-
cular, should be
observed, e.g. during
holidays.
*1
Only adjustable for mixer circuit M2.
*2
Only for weather-compensated control units.
Coding
Possible change
change
Address:
value
A2:0
Without DHW cylinder
priority applicable to
heating circuit pump and
mixer
A2:1
With DHW priority applic-
able to mixer: The mixer
is closed whilst DHW is
loaded; the heating cir-
cuit pump operates
A2:3
Reduced priority appl. to
to
mixer; i.e. the heating cir-
A2:15
cuit receives a reduced
amount of energy
A3:-9
Heating circuit pump ON/
to
OFF (see the following
A3:15
table)
Coding
*
1
*
1
53