Viessmann Vitodens 300 Service Instructions Manual page 53

Type wb3a, 49 and 66 kw gas fired wall mounted condensing boiler natural gas and lpg version
Hide thumbs Also See for Vitodens 300:
Table of Contents

Advertisement

Code 2
(cont.)
Coding in
Function mode
the as
delivered
condition
Address:
value
A2:2
With DHW cylinder
priority applicable to
heating circuit pump
and mixer
A3:2
*
2
Outside temperature
below 1 °C: Heating cir-
cuit pump ON
Outside temperature
above 3 °C: Heating cir-
cuit pump OFF
Note
When selecting a value
below 1 °C there will be
a risk of pipes outside
the thermal insulation
envelope of the house
freezing-up. The
standby mode, in parti-
cular, should be
observed, e.g. during
holidays.
*1
Only adjustable for mixer circuit M2.
*2
Only for weather-compensated control units.
Coding
Possible change
change
Address:
value
A2:0
Without DHW cylinder
priority applicable to
heating circuit pump and
mixer
A2:1
With DHW priority applic-
able to mixer: The mixer
is closed whilst DHW is
loaded; the heating cir-
cuit pump operates
A2:3
Reduced priority appl. to
to
mixer; i.e. the heating cir-
A2:15
cuit receives a reduced
amount of energy
A3:-9
Heating circuit pump ON/
to
OFF (see the following
A3:15
table)
Coding
*
1
*
1
53