Viessmann Vitodens 300 Service Instructions Manual page 40

Type wb3a, 49 and 66 kw gas fired wall mounted condensing boiler natural gas and lpg version
Hide thumbs Also See for Vitodens 300:
Table of Contents

Advertisement

Coding
Code 1
(cont.)
Coding in
Function mode
the as
delivered
condition
Address:
value
Gas type
1E:0
Natural gas operation,
defaulted by the boiler
coding card
Venting/filling
2F:0
Venting program dis-
abled
User no.
77:1
LON user number
DHW priority A1
A2:2
DHW cylinder priority
applicable to heating
circuit pump and mixer
DHW priority M2
A2:2
DHW cylinder priority
applicable to heating
circuit pump and mixer
Summer econ. A1
A5:5
*
1
With heating circuit
pump logic function
*1
Only for weather-compensated control units.
40
Coding
Possible change
change
Address:
value
1E:1
LPG operation, defaulted
by the boiler coding card
2F:1
Venting program enabled
2F:2
Filling program enabled
77:2
LON user number, adjus-
to
table from 1 to 99:
77:99
1 - 4 = boiler
5 = cascade
10 - ... = Vitotronic 050
99 = Vitocom
Note
Allocate each number
only once.
A2:0
Without cylinder priority
for heating circuit pump
A2:0
Without DHW cylinder
priority applicable to
heating circuit pump and
mixer
A2:1
DHW cylinder priority
only applicable to mixer
A2:3
Modulating DHW cylinder
to
priority
A2:15
A5:0
Without heating circuit
pump logic function