Viessmann Vitodens 300 Service Instructions Manual page 51

Type wb3a, 49 and 66 kw gas fired wall mounted condensing boiler natural gas and lpg version
Hide thumbs Also See for Vitodens 300:
Table of Contents

Advertisement

Code 2
(cont.)
Coding in
Function mode
the as
delivered
condition
Address:
value
80:1
With 5 seconds' time
delay for fault message;
message will be issued,
if a fault persists for at
least 5 seconds
81:1
Automatic summer/win-
ter changeover
88 :0
Temperature display in
Celsius
90:128
Time constant for calcu-
lating the adjusted out-
side temperature
21.3 hours
91:0
*
1
No external operating
mode changeover via
external extension
95:0
Without Vitocom 100
communication inter-
face
*1
Only for weather-compensated control units.
Coding
Possible change
change
Address:
value
80:0
Without time delay
80:2
Time delay adjustable
to
from 10 to 995; 1 step =
80:199
5 s
81:0
Manual summer/winter
changeover
81:2
The application of the
radio clock module will be
recognised automatically
81:3
Accept time via LON
88 :1
Temperature display in
Fahrenheit
90:0
Fast (low values) or slow
to
(high values) matching of
90:199
flow temperature subject
to set value if the outside
temperature changes;
1 step = 10 min
91:1
External heating program
changeover applies to
heating circuit without
mixer
91:2
External heating program
changeover applies to
heating circuit with mixer
91:3
External heating program
changeover applies to
heating circuit without
mixer and heating circuit
with mixer
95:1
With Vitocom 100 com-
munication interface;
automatic recognition
Coding
51