Code 2
(cont.)
Coding in
Function mode
the as
delivered
condition
Address:
value
80:1
With 5 seconds' time
delay for fault message;
message will be issued,
if a fault persists for at
least 5 seconds
81:1
Automatic summer/win-
ter changeover
88 :0
Temperature display in
Celsius
90:128
Time constant for calcu-
lating the adjusted out-
side temperature
21.3 hours
91:0
*
1
No external operating
mode changeover via
external extension
95:0
Without Vitocom 100
communication inter-
face
*1
Only for weather-compensated control units.
Coding
Possible change
change
Address:
value
80:0
Without time delay
80:2
Time delay adjustable
to
from 10 to 995; 1 step =
80:199
5 s
81:0
Manual summer/winter
changeover
81:2
The application of the
radio clock module will be
recognised automatically
81:3
Accept time via LON
88 :1
Temperature display in
Fahrenheit
90:0
Fast (low values) or slow
to
(high values) matching of
90:199
flow temperature subject
to set value if the outside
temperature changes;
1 step = 10 min
91:1
External heating program
changeover applies to
heating circuit without
mixer
91:2
External heating program
changeover applies to
heating circuit with mixer
91:3
External heating program
changeover applies to
heating circuit without
mixer and heating circuit
with mixer
95:1
With Vitocom 100 com-
munication interface;
automatic recognition
Coding
51