Viessmann Vitodens 300 Service Instructions Manual page 82

Type wb3a, 49 and 66 kw gas fired wall mounted condensing boiler natural gas and lpg version
Hide thumbs Also See for Vitodens 300:
Table of Contents

Advertisement

Troubleshooting
Checking and acknowledging faults
Displayed
Const.
fault code
F1
X
F2
X
F3
X
82
Weat-
System
her-
character-
comp.
istics
X
Burner in
fault state
X
Burner in
fault state
X
Burner in
fault state
(cont.)
Cause
Remedy
Flue gas tempera-
Check the
ture limiter has
heating sys-
responded
tem water
level. Vent
the heating
system.
Press reset
E no sooner
than after
20 minutes.
Temperature limiter
Check the
has responded
heating sys-
tem water
level. Check
the circula-
tion pump.
Vent the heat-
ing system.
Check the
temperature
limiter and
leads.
Press E.
The flame signal is
Check the
already present at
ionisation
burner start
electrode and
leads.
Press E.