Checking and acknowledging faults
Displayed
Const.
fault code
30
X
38
X
40
48
50
X
58
X
51
X
59
X
92
X
9A
X
93
X
9b
X
Weat-
System
her-
character-
comp.
istics
X
Burner
blocked
X
X
Mixer
closes
X
X
No DHW
heating
X
X
No DHW
heating
X
X
Control
mode
X
X
Control
mode
X
Troubleshooting
(cont.)
Cause
Remedy
Boiler temperature
Check the
sensor shorted out
boiler tem-
perature sen-
sor (see
page 87)
Boiler temperature
sensor lead break
Heating circuit M2
Check the
flow temperature
flow tempera-
sensor shorted out
ture sensor
Heating circuit M2
flow temperature
sensor lead break
Cylinder tempera-
Check the
ture sensor shorted
cylinder tem-
out
perature sen-
sor (see
page 87)
Cylinder tempera-
ture sensor lead
break
Cylinder tempera-
Check the
ture sensor 2
cylinder tem-
shorted out
perature sen-
sor (see
page 87)
Cylinder tempera-
ture sensor 2 lead
break
Solar: Collector
Check sensor
temperature sensor
shorted out
Collector tempera-
ture sensor lead
break
Solar: Sensor S3
Check sensor
shorted out
Sensor S3 lead
break
77