Viessmann Vitodens 300 Service Instructions Manual page 60

Type wb3a, 49 and 66 kw gas fired wall mounted condensing boiler natural gas and lpg version
Hide thumbs Also See for Vitodens 300:
Table of Contents

Advertisement

Coding
Code 2
(cont.)
Coding in
Function mode
the as
delivered
condition
Address:
value
E9:45
*
1
Speed of the variable
speed pump = 45 % of
max. speed in reduced
mode
Mixer circuit
F1:0
Screed drying function
disabled
*
1
*1
Only for weather-compensated control units.
60
Coding
Possible change
change
Address:
value
E9:0
Speed adjustable from 0
to
to 100 % of max. speed
E9:100
F1:1
Screed drying function
to
adjustable in accordance
F1:5
with 5 optional tempera-
ture time profiles (see
page 104)
Note
Observe the screed dry-
ing supplier's instruc-
tions.
Observe DIN 4725-2 or
local regulations. The
report to be provided by
the heating contractor
must contain the follow-
ing heat-up details:
&
Heat-up data with
respective flow tem-
peratures
&
Max. flow temperature
achieved
&
Operating condition
and outside tempera-
ture during handover.
The function continues
after power failure or
after the control unit has
been switched OFF. The
heating program rw
will be started, after the

Hide quick links: