Viessmann Vitodens 300 Service Instructions Manual page 57

Type wb3a, 49 and 66 kw gas fired wall mounted condensing boiler natural gas and lpg version
Hide thumbs Also See for Vitodens 300:
Table of Contents

Advertisement

Code 2
(cont.)
Coding in
Function mode
the as
delivered
condition
Address:
value
A8:1
*
1
Heating circuit M2
(mixer circuit) creates a
demand for the internal
circulation pump
A9:7
*
1
With pump idle per-
iod: Heating circuit
pump OFF in case of
set value modification
(by changing the oper-
ating mode or changing
the set room tempera-
ture)
b0:0
*
1
With remote control:
Heating mode/reduced
mode: Weather-com-
pensated
b2:8
With remote control unit
and for the heating cir-
cuit, heating with room
temperature hook-up
must be encoded:
Room influence factor
8
*
2
*1
Only for weather-compensated control units.
*2
Change the coding for the heating circuit without mixer A1 or for mixer circuit M2, if the
remote control unit affects that heating circuit.
Coding
change
Address:
value
A8:0
A9:0
A9:1
to
A9:15
b0:1
*
2
b0:2
b0:3
b2:0
b2:1
to
b2:64
Coding
Possible change
Heating circuit M2 (mixer
circuit) creates no
demand for the internal
circulation pump
*
1
Without pump idle per-
iod
With pump idle time,
adjustable from 1 to 15
Heating mode: Weather-
compensated
Reduced mode: With
room temperature hook-
up
Heating mode: With room
temperature hook-up
Reduced mode: Weather-
compensated
Heating mode/reduced
mode: With room tem-
perature hook-up
Without room influence
Room influence factor
adjustable from 1 to 64
57