Coding
Code 2
(cont.)
Coding in
Function mode
the as
delivered
condition
Address:
value
97:0
*
1
The outside tempera-
ture of the sensor con-
nected to the control
unit is utilised internally
98:1
Viessmann system
numbers (in conjunction
with monitoring of sev-
eral systems via Vito-
com 300)
9b:70
Minimum set boiler
water temperature in
case of external
demand
9C:20
*
1
Monitoring LON users
When there is no
response from a user,
values defaulted inside
the control unit continue
to be used for a further
20 minutes. Only then
will a fault message be
triggered.
9F:8
*
1
Differential tempera-
ture 8 K; only in con-
junction with a mixer
circuit
Boiler circuit, mixer circuit
A0:0
*
1
Without remote con-
trol
*1
Only for weather-compensated control units.
52
Coding
Possible change
change
Address:
value
97:1
Outside temperature is
adopted by the LON BUS
97:2
The outside temperature
of the sensor connected
to the control unit will be
utilised internally and
transmitted via LON BUS
to any connected Vitotro-
nic 050.
98:1
System number adjusta-
to
ble from 1 to 5
98:5
9b:1
Set temperature adjusta-
to
ble from 1 to 127 °C
9b:127
9C:0
No monitoring
9C:5
Time adjustable from 5 to
to
60 minutes
9C:60
9F:0
Differential temperature
to
adjustable from 0 to 40 K
9F:40
A0:1
With Vitotrol 200 (auto-
matic recognition)
A0:2
With Vitotrol 300 (auto-
matic recognition)