Viessmann Vitodens 300 Service Instructions Manual page 52

Type wb3a, 49 and 66 kw gas fired wall mounted condensing boiler natural gas and lpg version
Hide thumbs Also See for Vitodens 300:
Table of Contents

Advertisement

Coding
Code 2
(cont.)
Coding in
Function mode
the as
delivered
condition
Address:
value
97:0
*
1
The outside tempera-
ture of the sensor con-
nected to the control
unit is utilised internally
98:1
Viessmann system
numbers (in conjunction
with monitoring of sev-
eral systems via Vito-
com 300)
9b:70
Minimum set boiler
water temperature in
case of external
demand
9C:20
*
1
Monitoring LON users
When there is no
response from a user,
values defaulted inside
the control unit continue
to be used for a further
20 minutes. Only then
will a fault message be
triggered.
9F:8
*
1
Differential tempera-
ture 8 K; only in con-
junction with a mixer
circuit
Boiler circuit, mixer circuit
A0:0
*
1
Without remote con-
trol
*1
Only for weather-compensated control units.
52
Coding
Possible change
change
Address:
value
97:1
Outside temperature is
adopted by the LON BUS
97:2
The outside temperature
of the sensor connected
to the control unit will be
utilised internally and
transmitted via LON BUS
to any connected Vitotro-
nic 050.
98:1
System number adjusta-
to
ble from 1 to 5
98:5
9b:1
Set temperature adjusta-
to
ble from 1 to 127 °C
9b:127
9C:0
No monitoring
9C:5
Time adjustable from 5 to
to
60 minutes
9C:60
9F:0
Differential temperature
to
adjustable from 0 to 40 K
9F:40
A0:1
With Vitotrol 200 (auto-
matic recognition)
A0:2
With Vitotrol 300 (auto-
matic recognition)