Viessmann Vitodens 300 Service Instructions Manual page 61

Type wb3a, 49 and 66 kw gas fired wall mounted condensing boiler natural gas and lpg version
Hide thumbs Also See for Vitodens 300:
Table of Contents

Advertisement

Code 2
(cont.)
Coding in
Function mode
the as
delivered
condition
Address:
value
F2:8
*
2
Time limit for party
operation 8 hours or
external operating
mode changeover via
push button
F5:12
Run-on time of the inter-
nal circulation pump in
heating mode
F6:0
*
4
In "DHW only" operat-
ing mode, the internal
circulation pump is per-
manently OFF
F7:0
*
4
In "Standby mode",
the internal circulation
pump is permanently
OFF
*2
Only for weather-compensated control units.
In heating program rw, the party mode ends automatically when changing over to
*3
operation with standard room temperature.
*4
Only for constant temperature control units.
Coding
change
Address:
value
F1:6
to
F1:15
F2:0
F2:1
to
*
3
F2:12
F5:0
F5:1
to
F5:20
F6:1
to
F6:24
F6:25
F7:0
F7:1
to
Coding
Possible change
screed-drying function
has been completed or if
the address is manually
set to 0.
Constant flow tempera-
ture 20 °C
No time limit for party
mode
Time limit adjustable from
*
3
*
3
1 to 12 hours
No run-on time of the
internal circulation pump
Run-on time of the inter-
nal circulation pump
adjustable from 1 to
20 minutes
In "DHW only" operating
mode, the internal circu-
lation pump will be
started 1 to 24 times per
day for 10 minutes
respectively
In "DHW only" operating
mode, the internal circu-
lation pump is perma-
nently ON
In "Standby mode", the
internal circulation pump
is permanently OFF
In "Standby mode", the
internal circulation pump
61